Preparing to Start the Pump – Deep Well
Open control valve
as far as possible
and fill pump and
piping through
priming port
or priming tee.
280 0395
Figure 15: Fill Pump
Replace all
fill plugs and
close control
valve completely.
556 0395
Figure 16: Prime Pump
A-Open Control Valve
B-Watch for Pressure Gauge to Flutter
C-Close Control Valve until Pressure
Stabilizes
Figure 17: Set Control Valve
For parts or assistance, call Flotec Customer Service at
Never run pump dry. Running pump without water may cause
pump to overheat, damaging seal and possibly causing burns to persons
handling pump. Fill pump with water before starting.
Never run pump against closed discharge. To do so can boil
water inside pump, causing hazardous pressure in unit, risk of explosion
and possibly scalding persons handling pump.
Step 1. Open the control valve as far as possible (see Figure 15). Then
remove the priming plug from the pump and fill the pump, fill all
piping between the pump and the well, and make sure that all
piping in the well is full. If you have also installed a priming tee in
the suction piping, remove the plug from the tee and fill the suction
piping.
Step 2. Replace all fill plugs and close the control valve completely
(Figure 16).
Step 3. Power on! Start the pump and watch the pressure gauge. The
pressure should build rapidly to 50 PSI as the pump primes.
Step 4. After 2 or 3 minutes, the gauge should show pressure. If not, stop
the pump, remove the fill plugs, reopen the control valve, and refill
the pump and piping. You may have to repeat this two or three
times in order to get all the trapped air out of the piping. Don't for-
get to close the control valve each time before you start the pump.
Step 5. When pressure has built up and stabilized at about 50 PSI, slowly
open the control valve (see Figure 17) and let the pressure drop
until the pressure gauge needle starts to flutter. When the needle
flutters, close the valve just enough to stop the flutter (see Figure
17). Your pump is now operating at its most efficient point.
Step 6. After the pump has built up pressure in the system and shut off,
check the pressure switch operation by opening a faucet or two and
running enough water out to bleed off pressure until the pump
starts. The pump should start when pressure drops to 30 PSI and
stop when pressure reaches 50 PSI. Run the pump through one or
two complete cycles to verify correct operation. This will also help
clean the system of dirt and scale dislodged during installation.
Congratulations on a successful installation.
If you were unsuccessful, please refer to the Troubleshooting section
(Page 13) or call our customer service technical staff.
Thank you for purchasing Flotec Products.
281 0395
1-800-365-6832
11