Weight
R407c (Kg)
Model
(Kg)
(Kg)
PSH 030
83
0.68
PSH045
83
0.68
PSH065
83
1.1
PSH090
83
1.1
Calibration values
PSH 030-090

8.3 TECHNICAL DATA

MIN.- MAX
Ambient Temperature
Amb
Refrigerant
During
transport
and stocka-
ge
CO2
Equivalent
1.21
1.21
0-50°C
1.95
1.95
Hot gas valve
Fan pressure Switch
9 - HGV
4.6-5.0 bar
Compres-
sed
air inlet
F.L.A.[A]
After
Tempera-
installa-
ture
tion
230V ±10%
In
1ph/50Hz
4.2
5-50°C
5-65°C
10.6
High pressure Switch
12-PV
15-HP
ON: 18 bar
28 bar
OFF: 14 bar
PSH 030-090
Connections
Minimum
section
validated
Compressed
Condensate
cable for
air inlet
drain
electrical
air outlet
connection
Ø [mm2]
BSPT-F
BSPP-F
3G1.5
1" 1/4
1/4"
Air - Side Max
Working Pressure
50 bar
Sound
pressure
level
[dB (A)]
55
High temperature
safety thermostat
16-ST
130°C
7

Publicidad