3 Product description
3.1
Preparations before the assembly
The safety set can be connected laterally to a PAW modular distribution manifold of the same
nominal diameter. The mounting side is determined because of the "groove and spring" version
of the sealing strips!
NOTICE
The connection sleeve for the safety set must be directed forward
or backward! If the connection sleeve is directed upward or
downward, the flow and return chambers are connected which
leads to unwanted circulation!
B-4
Safety set DN 25
99525x3-mub-ml – V01
The safety set is designed to equip a PAW
modular distribution manifold subsequently
or additionally with a pressure relief valve
and with a connection for an expansion tank.
This is necessary when the boiler (with
safety devices) can be isolated or when the
boiler (primary) is separated from the heat
distribution (secondary) with a heat
exchanger.
3 Product description
2017/01