Installation Of The Comfocool Q600 - Zehnder Pumpen ComfoCool Q600 Manual Del Instalador

Tabla de contenido

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

  • MEXICANO, página 61

4.2 Installation of the ComfoCool Q600

Transport and unpacking
Take care when transporting and unpacking the unit.
Only transport it in an upright position. Keep it upright
when unpacking it. Make sure the packing material is
disposed of in an environmentally friendly manner.
Checking delivery
Contact your supplier immediately in case of damage or
an incomplete delivery. Besides the ComfoCool Q600,
the delivery should include:
■ 2x adaptor plates of high-grade polypropylene foam;
■ 4x rubber seal rings;
■ Power cable;
■ Data cable for data exchange with the heat-recovery
unit;
■ Manual;
■ Plastic design front;
■ 2x screws (Torx 30) for plastic design front.
The ComfoCool Q600 is supplied as type L for left-
handed version of the heat-recovery unit and as type
R for right-handed version of the heat-recovery unit.
Check that the designation on the ComfoCool Q600s
identification plate corresponds with the designation in
the heat-recovery units software.
Assembly
The ComfoCool Q600 should be mounted on top of
the heat-recovery unit. The heat-recovery unit must be
mounted on a support frame that is level and stands
on a suitably solid floor. Each distinct assembly step is
outlined below:
1. Assemble the support frame according to the
instructions supplied. Then place it on the floor and
ensure the upper surface is level using the adjustable
feet.
2. Place the heat-recovery unit on top of the support
frame.
3. Remove the hygienic covers of the heat-recovery unit.
4. Place the two adapter plates over the spigot
openings of the heat-recovery unit. Check that the
metal bracket is pointing to the front of the heat-
recovery unit. The adapter block marked with an L
must be placed on the left side of the heat-recovery
unit. The adapter block marked with an R must be
placed on the right side of the heat-recovery unit.
5. Place the four rubber seal rings over the spigot
openings. Check that the seals are creating an
effective seal between the spigot and the adapter
plates.
6. Connect the data cable to a free ComfoNet plug-in
connection on the heat-recovery unit.
a. 12 Vdc: Red
b. GND: Black
c. CAN_H: Yellow
d. CAN_L: White
7. Lay the cable through the cable tray of the heat-
EN - 26
recovery unit.
8. Mount the ComfoCool Q600.
a. Note: never lift the ComfoCool Q600 alone. It is heavy
and must be mounted precisely;
b. The ComfoCool Q600s feet should fit in the recesses
of the adaptor plate. Make sure the seals do not
dislodge while doing this.
9. Fix the fall protection firmly to the wall. To prevent
vibrations being transmitted to the wall, ensure that
the fall protection is not under tension.
10. Mount the plastic design front on the unit. Check
that the top of the plastic design front falls in the top
of the unit before you screw the bottom side to the
adaptor plates.
11. Connect the data cable to a free ComfoNet plug-in
connection on the unit.
a. 12 Vdc: Red
b. GND: Black
c. CAN_H: Yellow
d. CAN_L: White
12. Connect the condensation drain to the domestic
waste-water system via a siphon or a water lock of
at least 60mm. Ensure the siphon or water lock is
full of water. The condensation drains of the heat-
recovery unit and the ComfoCool Q600 must always
be connected with a siphon.
13. Remove the hygienic covers of the unit and
connect the air ducts.
14. Please refer to the heat-recovery unit manual for
further installation instructions for the heat-recovery
unit.
15. Connect the main supply of the heat-recovery unit
and ComfoCool Q600.
For safety reasons, the ComfoCool Q600 will
pause for 15 minutes before initially activating the
compressor.

Publicidad

Tabla de contenido
loading

Tabla de contenido