FUNCTIONS: DESCRIPTION
ATTENTION: each variation on the Dip-Switches for the required functions will be executed with the next opening or
closing command.
ADJUSTMENT OF TORQUE:
The adjustment of the torque by the Trimmer must be sufficient to move the gate.
Before programming, it is advisable to position the Trimmer in proportion to the weight and length of the
gate. This adjustment also determines the torque on slowing down and impact resistance with an obstacle.
Too high torque in relation with the inertia of the gate leads to incorrect installation according to safety standards
EN 12445 and EN 12453. Therefore, once the torque applied to the automated gate is adjusted, the installer must
check the torques as determined by the regulations EN 12445 and EN 12453 documented in the "Safety Standards"
manual that the manufacturer provides on request.
Automatic / Semiautomatic:
Automatic cycle: upon open command, the gate opens, stops in pause (for the
time set in the Pause Trimmer), then recloses automatically.
Pause time is resumed upon passage on the external photocells.
Semiautomatic Cycle: with an open command the gate moves to opening. To close
the passage, it is necessary to give the close command.
Reverse direction upon contact with obstacle:
This function enables the inversion of the movement on contact with an obstacle.
- Opening phase: the function reverses the direction, freeing the obstacle. Gate
stopped, waiting for a new command.
- Closing phase: the function reverses the direction up to the opening limit switch.
The sensitivity of the function is proportional to the torque as set by the Master and
Slave Torque Trimmer
Please note: If the gate detects an obstacle for 5 consecutive times during a
complete open - stop - close cycle, the gate will remain open and the lamp will
flash with a Blue light. Waiting for a command.
Closing on passing through the pair of photocells:
This function enables automatic closing 3s after passage through the pair of internal
photocells
DSA: Checks photocells before start up
Device for Safety Autotest = before every gate movement, if this function is enabled
and photocell projectors outputs 13-14 are powered, a check is performed of all
safety devices to ensure they are free from obstacles. If they are not, the gate opener
will not start and this will be signalled on the Bart with the light flashing amber-blue
alternatively.
Opening by way of External clock:
Connection: connect the NO contact of the Clock to terminal 4 OPEN and terminal 3
COMMON in parallel, and enable the automatic closing by Dipswitch 3= ON.
Operation: program the opening time on the clock.
At the time set, the gate will remain open (the flasher goes off ) and it will not accept
other commands (not even radio) until the time that has been set on the clock runs
out. Once that time has expired, after the pause time, the automatic closing will
follow.
of the
FUNCTIONS
of the
Description
BART 350
with articulated arm
DIP-SWITCH 3:
ON: Closes in Automatic Mode
OFF: Semiautomatic
3
DIP-SWITCH 6:
ON:
to prevent the gate travel from being reversed
6
too easily in case of incorrect installations.
DIP-SWITCH 9:
ON: Enables the automatic closing after the
passage through the pair of photocells
9
OFF: No automatic closing
DIP-SWITCH 10:
ON: DSA control of the photocells. The
photocell projectors outputs 13-14 must be
10
powered
OFF: No DSA control on the photocells
ON:
3
Instructions
Dip-switches and LED indication
of their functions
Pause Trimmer: the pause time
can be adjusted in the automatic
mode from 1s to 120s.
Decreases sensitivity on closing gate stop,
Torque Trimmer of Bart Master (M):
adjusts the torque applied on
the gate by the Bart Master and,
in proportion, the resistance to
contact with an obstacle.
Torque Trimmer of Bart Slave (S):
adjusts the torque applied on
the gate by the Bart Slave and,
in proportion, the resistance to
contact with an obstacle.
External clock
NO
Closes in Automatic Mode
pg.
27