Horizontal Unit Heater 10KW - 240V - 1 or 3 Phase
User's Manual
Product Specification
Model
Manufacturer
Model
Length Inches
Width Inches
Height Inches
Wire Size For
Installation
Net Weight Lbs
Construction
Btu High
Cfm High
Outlet Air
Temperature
Voltage
Phase
Amps
Watts
Kilowatts
Circuit Breaker
Amp rating
Safety Tip-Switch
Limited Warranty
Years
Certification
INSTALLING INSTRUCTIONS
All wiring must be installed by a certified
electrician according to the local electrical
codes. The ceiling heater must be grounded in
accordance with all national and local building
All Wiring procedures and connections shall be in
accordance with the national and local codes having
jurisdiction.
Prior to installation:
Disconnect the main supply connection.
Supply cables shall be 6 AWG (13.3 mm2) copper wires.
The heater must be connected to individual branch circuit
protected by 60 Amp circuit breaker only.
Supply cables must be equipped with a dual pole circuit
breaker rating at least 240V 60A/pole as main cutoff switch
of power connection to the heater.
Wiring compartment for accommodating supply cables and
pigtail leads are adequate and measured free space of
2524.67 cm3 .
246102
Power
PH-9100WTX
Terminal
Block
18.11
16.73
16.06
6AWG
48.24
Cold Rolled Steel
34,129
600
221°F @ Ambient
Temp. 77°F
240V
1 or 3
41.7
10,000
10
60A
No
1
UL,cUL
codes.
Wiring Diagram
G
H1/3300W
W
Fan and Heater
Switch
Limit Overheat Cutout
Switch selector for build in
thermostat or wall thermostat
3 Phase Wiring
NOTE:
1. 1 Phase Connection
2. 3 Phase Connection
For 3 Phase Wiring:
Connect lead wire [ W ] to terminal point [ W1 ]
and lead wire [ T ] to terminal point [ T1 ]
High temperature, risk of fire, keep electrical
cords, drapery, furnishings, and other
combustibles at least 3 feet (0.9 m) from the
front of the heater and away from the side
To reduce the risk of fire, do not store or use
gasoline or other flammable vapors and
3
H3/3300W
H2/3300W
3 Phase
Terminal Block
Not included
Terminal A
(Wall thermostat)
External temperature control
(Build in thermostat)
Temperature control
NOTE:
To use an external temperature controller (a
wall thermostat). Detached the black wire
that short current Terminal "A", and then insert
the lead wires from wall thermostat to Terminal
A and secured. Switch the selector switch to
Wall thermostat to use it.
For single phase connection, please connect
to L1 and L3.
For 3 phase connection, move red wire
marked "W" connecting terminal L1 to W1 and
move red wire marked "T" connecting terminal
L3 to T1.
and rear.
liquids in the vicinity of the heater.