FAULT CONDITIONS
If a Fault condition occurs the Fault triangle symbol will switch ON
steady (Warning) or flash (Trip). The user menu display item will show a 'Fault
Code' dependant on the fault.
Fault Codes.
SERVICE DUE COUNTDOWN TIMER
If the service due countdown timer reaches 0 (Zero) hours the Service
and Alarm symbols will flash and the service Alarm (Warning) code will be
displayed. The Alarm code can be reset but the service symbol will remain on
the display until the service due timer is reset; the service hours will continue
to decrement in negative hours. The service countdown timer can be reset,
using the menu routine, when the required service has been carried out. Set
to any value greater than 0 (Zero) hours before reset.
MENU ROUTINE
Parameters, Values and Options can be adjusted and set using the Menu
Routines. These are two menu lists:
1.
Operational Menu - Access Code "0009"
2.
Configuration Menu - Accessable just for Ingersoll Rand authorised
service personel.
To access a menu, Stop the compressor
first, then press the Up and Down buttons
simultaneously. After several seconds the display
will show four "0" characters; the first character
will flash. Press Up and Down to adjust the first
character to match the first character to match
the first character of the required access code.
Press Enter to increment to the second code
character.
When all four character has been set, and the
last code character is flashing, press Enter. If
the access code is correct for the access to one
of the two menus the first menu item of the
appropriate menu will be displayed. If the access
code is incorrect the display will return to the
normal operational display.
To select a menu item for adjustment press Up
or Down until the menu item is displayed. To
adjust an item setting press 'Enter' , the value or
option will flash. Press Up or Down to adjust as
required then press Enter to store in memory.
To exit a menu and return to the normal
operational display, at any time, Press Reset.
Any adjustment that has not to be entered to
memory will be abandoned and previous setting
maintained.
EN-36
RELEASED 16/Dec/2014 10:49:53 GMT
The compressor will maintain pressure between the set Pu (Unload Pressure
Set Point) and (PL) (Load Pressure Set Point). When Pressure reaches the set
'Pu' level the compressor will unload. When pressure falls to the 'PL' level the
compressor will load.
NoTE:
•
•
•
•
When the main motor stops the compressor will allow a period of blowdown
(the Blowdown Time) before a motor start can be re-initiated. A motor
re-start is inhibited during this time period. This time is intended to allow
internal pressure (or sump pressure) to be vented before a motor start
sequence is permitted. Set to 0 (zero) seconds if not required.
•
When the Stop button is pressed the compressor will unload and the main
motor will continue to run for the set Stop Time. This time is intended to
allow internal pressure (or sump pressure) to reduce before the compression
element is stopped; preventing potential oil blow-back through the
compression element and air filter. The stop time is initiated from the
moment the compressor is unloaded. If the compressor has been offload for
a period of time prior to a stop command the time is automatically reduced
accordingly. If the compressor is stopped after the compressor has been
running offload for the stop time, or longer, the compressor is stopped
immediately; no stop time is applied. Set to 0 (zero) seconds if not required.
OPERATIONAL MENU
Table 20 : operational Menu
Item
1
1.Pu
Upper Pressure Set Point
2
1.PL
Lower Pressure Set Point
3
1.bt
Blowdown time
4
1.St
Stop time
5
1.P-
Pressure Display Unit
6
1.t-
Temperature Display Units
Do not change factory setting of the upper and lower pressure set
points
For TAS version machines maximum operating pressure cannot
exceed rated discharge pressure��
Do not change factory setting of Auto Restart Time��
Blowdown Timer:
Stop Time:
Description