Alarm Output - Milltronics POINTEK VLS 200 Manual De Instrucciones

Tabla de contenido

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

Specifications
Note:
Siemens Milltronics makes every attempt to ensure the accuracy of these
specifications but reserves the right to change them at any time. Please ensure these
are the most recent specifications.
Check our web site at www.siemens-milltronics.com or contact your representative
for the most up-to-date information.
Power
• 19 to 230 Vac, +10%, 50 to 60 Hz, 8VA
• 19 to 55 Vdc, +10%, 1.5W

Alarm Output

• relay delay
– approx. 1 second from loss of vibration
– 1 to 2 seconds from resumption of vibration
• relay failsafe: high or low, switch selectable
• relay 8A at 250 Vac, non-inductive
relay 5A at 30 Vdc, non-inductive
Mechanical
Enclosure material
• epoxy coated aluminum
Process Connection
• thread 1½" NPT, R 1½" DIN 2999 (tapered)
• tine material: stainless steel 316Ti (1.4571)
• thread material: stainless steel 303 (1.4305)
Conduit entry
• 2 x M20 x 1.5
• 2 x ½" NPT
Weight
• approx. 1.9 kg, + 2.5 kg/m extension tube
Signal Delay
• probe free to covered: approx. 1 sec
• probe covered to free: approx 1 to 2 sec