6.5.- MAPA PICS
PICS
Vendor Name:
Product Name:
Product Model Number:
Application Software Version:
firmware Revision:
BACnet Protocol Revision: 10
Product Description:
Electrical energy meter
BACnet Standardized Device Profile (Annex L)
x
List all BACnet Interoperability Building supported (see Annex K in BACnet Addendum 135d):
DS-RP-B Read Property
DS-WP-B Write Propery
DS-RPM-B Read Property Multiple
DM-DDB-B Dynamic Device Binding
DM-DOB-B Dynamic Object Binding
DM-DCC-B Device Communication Control
DM-RD-B Reinitialize Device
Which of the following device binding methods does the product support? (check one or more)
x
x
Standard Object Types Supported:
Analog Input Object Type
1. Dynamically creatable using BACnet's CreateObject service?
2. Dynamically deleatable using BACnet's DeleteObject service?
3. List of optional properties supported:
4. Listo f all properties that are writable where not otherwisa required by this standard
5. List of proprietary properties:
6. List of any property value range restrictions:
Properly Identifier
Object_Name
DESCRIPTION
Tensión fase-neutro
Corriente
Potencia activa
Potencia reactiva
Factor de potencia
Tensión fase-neutro
Corriente
Potencia activa
206
0.7.1
BACnet Application Specific Controller (B-ASC)
Recive Who-Is, send I-Am (BIBB DM-DDB-B)
Recive Who-Has, send I-Have (BIBB DM-DOB-B)
max 6 characters
Voltage phase to
neutral
Current
Active power
Reactive power
Power factor
Voltage phase to
neutral
Current
Active power
CIRCUTOR
CVM-B100
|
CVM-B150
0823
1.0
SyMBOL
V 1
A 1
kW 1
kvar 1
PF 1
V 2
A 2
kW 2
CVM-B100 - CVM-B150
No
No
max_pres_value
ID OBjECTS OBjECT NAME
AI0
Ph2NU1
AI1
Ph1Current
AI2
ActPwrPh1
AI3
ReactPwrPh1
AI4
PwrFactPh1
AI5
Ph2NU2
AI6
Ph2Current
AI7
ActPwrPh2
Manual de Instrucciones
min_pres_value
UNITS
V
A
kW
kvar
PF
V
A
kW