Descargar Imprimir esta página

yellow jacket AccuProbe UV Manual De Instrucciones Y Funcionamiento página 5

Publicidad

Idiomas disponibles

Idiomas disponibles

Using the SmartAlarm Display
1.
The SmartAlarm will not display a num-
ber (1 through 9) until a leak is sensed.
Once a leak is sensed, the numbers on the
display will gradually increase.
2.
Use the SmartAlarm display to "zero in"
on the leak source by watching the num-
bers climb higher as the leak source is
approached.
3.
Once the leak source has been located,
always wait for the maximum number
to be displayed to determine the size of
the leak.
4.
Lower numbers (approximately 1 to 3)
indicate that the leak size is less than
0.1 oz/yr. and may not require repairing
at this time – depending on the amount
of gas in system. NOTE: Multiple small
leaks in a system are cumulative and
may require that all system leaks should
be repaired.
AccuProbe II
1.
TURN ON: Press the ON/OFF button once to
turn on and again to turn off.
WARM UP: The detector automatically starts
2.
heating the sensor. During the heating cycle,
the detector will sound a slow "beep
up time is usually about 20 SECONDS or less.
For maximum sensitivity, wait an additional
two minutes after normal warm-up.
3.
READY: The detector is ready to begin
searching for leaks when the green sensitivity
LED turns on. The audio "beep" increases in
frequency.
Sensitivity
level
indicators
Power
ON/OFF
AccuProbe II Keypad
Adjusting the sensitivity levels
To choose another sensitivity level, press the
Sensitivity button. The LED below each level
will change indicating the new setting.
The leak detector will default to the NORM
sensitivity level automatically once the unit
comes out of the warm-up cycle and the green
LED turns on.
Using the Leak Standard
Use the leak standard to determine that the
leak detector performs to specifications.
1.
2.
3.
. Warm
"
Sensitivity
adjust
Lift off the plastic sealing cap on the top
of the LEAK STANDARD.
POWER ON the unit. After WARM UP
and when READY expose the sensor
directly to the small hole in the top of the
bottle cap. The beep rate should increase
to an alarm. For the AccuProbe, the
SmartAlarm should display a number
greater than 2. If the SmartAlarm fails to
display 2 or above, leave the detector on
for approximately 15 to 30 seconds long-
er and retest. This indicates that
sensor and electronic circuit are func-
tioning properly.
Replace plastic cap seal after leak test.
Note: Replace the leak standard when the
green color is no longer visible.
Removable sealing cap
Non-removable cap with
leak opening
Non-ozone depleting chem-
ical has green color
Leak Standard Bottle
the
5

Publicidad

loading

Productos relacionados para yellow jacket AccuProbe UV

Este manual también es adecuado para:

Accuprobe ii69336693376933869354