Wiring Connections; Drive Sensor Cable Connections - Franklin Electric SubDrive Duplex Alternator Manual Del Usuario

Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

Wiring Connections

1.
Verify that the power has been shut off at the main breaker.
2.
Open the cover to the alternator.
Drive Connections
3.
Connect a two-conductor pressure sensor cable from drive 1 to the
alternator's terminal block labeled SD1 on the right side. The red and
black wire connections are interchangeable. (See Figure 2 below).
Whichever drive unit is connected to the SD1 terminal will be the
primary system first. The drive unit connected to the SD2 terminal will
be the backup system first.
A. If connecting to a SubDrive300, use the supplied two-conductor
pressure sensor cable. Cut the terminals off both ends of the red
and black leads from the existing four-conductor cable. Leave
only the green and white leads linking the pressure shut-off
switch to its connections on the SubDrive300.
B. For all other SubDrives, cut off the quick connect ends and strip
the wire to make a two-conductor cable with stripped leads at
both ends.
4.
Repeat step 3 for drive 2, but connect drive 2's pressure sensor cable
to the alternator's terminal block labeled SD2 on the right side.
Figure 2: Drive Sensor Cable Connections
SubDrive300
Alternator
1
2
1
2
1
2
1
2
PS-HI
PS-LO
SD1
SD2
12 VAC
PRESSURE
DRIVES
ALARM
SENSORS
24V-1A
To Pressure Shut-off Switch
Note: If using a NEMA 4 the quick connects or stripped leads may be used.
SubDrive Duplex Alternator
(A)
PRESSURE
INT
NO
NO
SENSOR
SHUT-OFF
FAN
RELAY
COM
PFC
INV
FAN
FAN
PRESSURE
SENSOR
SHUT-OFF
(Cut black and red wires; leave only
the green and white connected to
the pressure shut-off switch.)
Alternator
INT
NO
NO
1
2
1
2
FAN
PS-HI
PS-LO
12 VAC
PRESSURE
ALARM
SENSORS
RELAY
24V-1A
COM
PFC
INV
FAN
FAN
(B)
1
2
1
2
SD1
SD2
DRIVES
SubDrive
9

Hide quick links:

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

5850012000

Tabla de contenido