Energi Savr Node
Step-by-step installation instructions
Step 1: Mounting the unit
Note: Mount the Energi Savr Node unit in a position where it can
be easily located and accessed if service or troubleshooting is
necessary.
• Remove metal outer panel cover.
• Remove internal plastic line voltage shield.
• For indoor use only!
• NEMA, Type 1 enclosure, IP20.
• Mount panel where audible noise is acceptable (internal relays
click).
• Mount panel so line voltage wiring is at least 6 ft (1.8 m) from
audio or electronic equipment and associated wiring (prevents
radio frequency interference).
• Install in accordance with all national and local electrical codes.
Step 2: Control power wiring
The Energi Savr Node unit operates at 120-277 V . Use the
following instructions to wire line voltage to power the Energi
Savr Node unit.
WARNING! Danger of Shock. May result in serious
injury or death. DO NOT WIRE WHEN LIVE! Switch off
power to all power feeds via circuit breaker before wiring
or servicing the Energi Savr Node unit.
Buttons and LEDs in the unit are used for programming
and troubleshooting. If wiring is exposed when accessing
buttons and LEDs, the unit must be accessed by a certified
electrician, following local codes.
1. Remove metal outer panel cover.
2. Remove internal plastic line voltage shield.
3. Use 14 AWG to 12 AWG (2.5 mm
pending on breaker rating) to feed the control power wiring. The
Energi Savr Node unit draws less than 0.5 A.
4. Wire the line voltage cables to the terminals labeled H (Hot) and
N (Neutral). A two-position terminal block is provided.
5. The Energi Savr Node unit is grounded through the ground bar.
Attach the ground wire.
6. Reinstall internal plastic line voltage shield.
7. Turn on the circuit breaker to power up the Energi Savr Node
unit. The 'Wired' LED on the Energi Savr Node unit will light
when properly energized. If the LED does not light, turn off
power, then check the control power wiring.
8. Turn power off.
Energi Savr Node
0-10V / Softswitch
TM
English
0-10 V / Softswitch
TM
to 4.0 mm
) conductors (de-
2
2
Installation Guide
®
Español
Français
|
Installation Guide
®
Mechanical Dimensions
All dimensions shown as inches (mm)
9.25
(234.95)
1.66
(42.16)
7.50
(190.50)
Line Voltage Shield
Control Power Wiring
Control Power Wiring:
• Two (2) 14 AWG to 12 AWG
(2.5 mm
2
to 4.0 mm
2
)
• Strip length: 3/8 in (8.5 mm)
• Torque: 7 in-lb (0.79 N
m)
•
Português
1.31
(33.27)
1.22
(30.99)
3.16
0.88
(80.26)
(22.35)
1.00
(25.40)
Do not
use side
knockouts
11.25
(285.75)
13.25
(336.55)
0.20 (5.16) dia.
Typical 4 places
Neutral (N)
Hot (H)
Ground
Lutron
®
3
|