WARNING: Reverse functioning can only be selected when mode Set 1 is always higher than the mA signal.
Example n° 1: PUMP MODEL EXACTUS-CC, 10 L/H, 5 BAR, SIGNAL 4-20 mA.
Signal 4 mA = 0 l/h (0% pump flow rate)
Signal 12 mA = 5 l/h (50% pump flow rate)
Signal 20 mA = 10 l/h (100% pump flow rate)
Example n° 2: SAME MODEL, BUT WITH INVERSE SIGNAL: 20 - 4 mA
Signal 4 mA = 10 l/h (100% pump flow rate)
Signal 12 mA = 5 l/h (50% pump flow rate)
Signal 20 mA = 0 l/h (0% pump flow rate
•