Modbus Address
Protocol
Addresses
PLC Addresses
(Base 0) Hex
(Base 1) Decimal
14
Phase Angle Block
1003 - 1003
4100 - 4100 Phase A Current
1004 - 1004
4101 - 4101 Phase B Current
1005 - 1005
4102 - 4102 Phase C Current
1006 - 1006
4103 - 4103 Angle, Volts A-B
1007 - 1007
4104 - 4104 Angle, Volts B-C
1008 - 1008
4105 - 4105 Angle, Volts C-A
Status Block
1387 - 1387
5000 - 5000 Meter Status
1388 - 1388
5001 - 5001
Limits Status
1389 - 138A
5002 - 5003 Time Since Reset
9
Resets Block
4E1F - 4E1F 20000 - 20000 Reset Max/Min Blocks
4E20 - 4E20 20001 - 20001 Reset Energy Accumulators
Meter Programming Block
55EF - 55EF 22000 - 22000 Initiate Programmable Settings Update
55F0 - 55F0 22001 - 22001 Terminate Programmable Settings Update
55F1 - 55F1 22002 - 22002 Calculate Programmable Settings Checksum
55F2 - 55F2 22003 - 22003 Programmable Settings Checksum
55F3 - 55F3 22004 - 22004 Write New Password
e Electro Industries/GaugeTech
1
Description
7
Commands Section
3
3
3
3
6
Format
Range
SINT16
-1800 to +1800
0.1 degree
SINT16
-1800 to +1800
0.1 degree
SINT16
-1800 to +1800
0.1 degree
SINT16
-1800 to +1800
0.1 degree
SINT16
-1800 to +1800
0.1 degree
SINT16
-1800 to +1800
0.1 degree
--exnpch ssssssss
UINT16
bit-mapped
UINT16
bit-mapped
87654321 87654321
UINT32
0 to 4294967294
4 msec
4
5
UINT16
password
5
UINT16
password
5
UINT16
password
UINT16
any value
UINT16
UINT16
UINT16
0000 to 9999
Doc # ES145721 V1.07
Units or
Resolution
Comments
exnpch = EEPROM block OK flags
(e=energy, x=max, n=min, p=programmable
settings, c=calibration, h=header),
ssssssss = state (1=Run, 2=Limp, 10=Prog
Set Update via buttons, 11=Prog Set
Update via IrDA, 12=Prog Set Update via
COM2)
high byte is setpt 1, 0=in, 1=out
low byte is setpt 2, 0=in, 1=out
wraps around after max coun
meter enters PS update mode
meter leaves PS update mode via reset
meter calculates checksum on RAM copy
of PS block
read/write checksum register; PS block
saved in EEPROM on write
write-only register; always reads zero
#
Reg
Block Size:
42
read-only
1
1
1
1
1
1
Block Size:
6
read-only
1
1
2
Block Size:
4
write-only
1
1
Block Size:
2
read/conditional write
1
1
1
1
8
1
MM-4