I - INSTALLATION / CABLING :
1 - Installation conditions :
Upstream protection :
The user has to imperatively install an upstream two-pole circuit-breakers must be either AM
(for motor starting currents), D (delayed thermal) or magneto-thermal type, set to 10 I N .
Primary current consumed under nominal load :
TITAN Models
Primary Current I p eff.
2 - Cabling : (one cabinet)
When choosing the cross-sections of the cables, take account of the distance and the current running through them. The line
loss must not exceed 5% of the battery's nominal voltage (12V, 24V or 48V) at nominal current.
Remove the cover (screws); all connection terminals will be accessible.
Make all connections with power switched off (upstream breaker switch open), (use cable passages).
If batteries must be connected, remove fuse F2 from the TITAN board or disconnect one of the battery cables.
Install bracket around power supply cables very near to terminal block.
CONNECTION TABLE : (* only on 48V models)
TITAN Calibre
Junction blocks in mm²
CONNECTION TERMINAL
Mains
AC network ground
BATTERY output
OUTPUT / UTIL
Auxiliary Output *
TEL ground *
TITAN BOARD
Alarms
II- CONFIGURATION / START-UP / ADJUSTMENT :
1 - Configuration :
Selection of battery limitation current :
Set the charge current according to the type of battery used, through switch unit S1 of the TITAN board.
Battery manufacturers recommend that you recharge a battery for 10 to 12 hours with a recharging current of
C Ah / 10 for backed-up installations with slow discharge.
12V
24V
48V
48V
40A
32A
10A
16A
5A
8A
5A
8A
10A
16A
N br
2
4
4
1
4
4
2
16
16
2
16
16
2
4
4
1
16
16
6
4
4
Location :
To obtains the best performances from the appliance, install it
in a dry, ventilated room that is not excessively dusty. The
ideal ambient temperatures is between 10°C and 30°C.
Leave a space of 10 to 15 cm around the cabinet in order to
facilitate natural cooling.
Securing the Cabinet :
SLAT securing bracket (quick mounting and dismounting)
Position the SLAT wall securing bracket and then secure it
with three 5mm screws (supplied). Fit the cabinet on the
bracket.
48V
48V
48V
25A
32A
40A
11,5A
15A
18A
25A
32A
40A
4
4
4
4
35
35
35
35
4
4
16
16
4
4
7
ENGLISH
4
4
35
35
4
16
4