1. Safety Instructions
For skilled electricians and instructed
personnel in accordance with national
regulation, including the relevant standard and,
where applicable, in acc.with IEC 60079-17 on
electrical apparatus for explosive atmospheres.
The luminaires must not be operated in Zone 0
and Zone 20.
The tecnical data indicated on the luminaires
are to be observed.
Changes of the design and modifications to the
luminaires are not permitted.
The luminaires shall be operated as intended
and only in undamaged and perfectconditions.
Only genuine Cooper Cr
Cooper Cr
Cooper Cr
Cooper Cr
Cooper Crouse-Hinds, S.A.
ouse-Hinds, S.A.
ouse-Hinds, S.A.
ouse-Hinds, S.A. spare
ouse-Hinds, S.A.
parts may be used for replacement.
Repairs that affect the explosion protection, may
only be carried out by Cooper Cr
Cooper Cr
Cooper Cr
Cooper Crouse-Hinds,S.A.
Cooper Cr
or a qualified "electrician" and will subsequenctly
have to be cheked by an "expert".
Do not keep these operating instructions inside
the luminaire during opertion.
The national safety rules and regulations for
prevention of accidents and the following
safety instructions which are marked with an
(
) in theses operting instructions, will have
to be observed.
2.Conformity with standards
This explosion protected luminaires meets the
requeriments of IEC/EN 60079-1, IEC/EN 60079-7,
IEC/EN 61241-1 and EN60598. It also complies with
the
EC Directives for "Apparatus and protective
systems for use in explosive atmospheres"
(94/9/EC) and "Electromagnetic compatibility"
(89/336/EEC).
It has been designed, manufactured and tested in
accordance to the state of the art and according to
EN29001 (ISO9001).
The luminaire are suitables for use hazardous areas,
in Zone 1 and 2 acc. to IEC60079-10-1 Zones 21 and
22 acc. IEC 60079-10-2.
3. Technical data
Application
II2GD
Class I:
Exde IIC T
Class II:
Ex tD A21 IP67 T
Certificates:
LOM 02 ATEX2012X
IECEX-BKI 07.0031X
Others, contact us
Serie of types:
See Table 1
Lamps to be use
6)
:
See Table 1
Approval of the production
ATEX Quality assurance:LOM 02 ATEX 9040
Degree of protection
acc. EN60598:
IP 67
Insulation class
acc. EN60598:
I
Temperature of use:
-45
o
C to + 55
Rated voltage standard 230V + 5% - 10%.
50 Hz, λ≥0,85
On request:
220-240-250V; 50/60Hz
Material of enclosure:
Metal aloy aluminium
without Cu, painted
polyester grey.
Notes:
4) There are no limitation for the EV luminaries.
The symbol "X" is retened to the EVI luminaries, that they have the lamp certificate of -CE examination type.
5) See table 2, thermal class acc. the lamp used.
6) Non included.
Material of glass
Storage temperature in original
Packing
Terminals capacity:
Entries of cables
Indirect entry:
Dimensions:
4. Installation
¡The respective national regulations as well
as the general rules of engineering which
apply to the installation and operation of
explosion protected apparatus will have to be
observed!
¡Transport and storage of the luminaire is
permitted in original packaging only!
¡Pay attention when mounting or repairing the
luminaire, dont damage the fire-finish of the glass
adquired during moulding (abrasions, sanding,
etc.) that can weaking their mechanical functions!
Opening and closing the luminaires
ouse-Hinds,S.A.
ouse-Hinds,S.A.
ouse-Hinds,S.A.
ouse-Hinds,S.A.
¡The opening of luminaire always shall be
without voltage!
¡The luminaire is well closed when the
glass-collar and covers are completly
threaded on the luminaire enclosure!
See figures 5, 6 and 7
Dimensions for mounting:
Accesories for mounting:
Cooper Cr
Cooper Cr
See Cooper Cr
Cooper Cr
Cooper Crouse-Hinds, S.A.
Cable entries
¡Mounting the selected cable entries
(cableglands or seals acc. needs) acc. type
and dimensions of the main conection cable,
following their manufacturer instructions!
¡The cable entries devices has to be the
protection mode Exe!
¡Unused cabe entries have to be closed by a
correspondante certified blanking plug Exe.
If the original blanking plugs are used , these
must be tightened with 15 Nm torque!
Main conection:
Lamps mounting
¡Only must be mounting apropiated lamps
for the supplied luminaire. See indications in
the general label of the luminaire!
¡Referred to the discharge lamps with incorporate
ignitor, only use these manufactured in acc. with
the EC Directive of Electromagnetic compatibilty!
5)
5)
5.
Taking into operation
4)
4)
¡Prior to operation check the luminaire for
its proper funtioning and installation in
compliance with these operting instructions and
others applicable regulations!
Only carry out insulation measurements between PE
and external conductor L1 (L1, L2, L3) as well as
between PE and N.
-
measurement voltage: max. 1kV AC/DC
-
min. insulation: 2 MΩ
Then the luminaire have to be tightly closed.
o
C
Borosilicate
o
o
-40
C a + 60
C
See wiring diagram
2 x M25 x 1,5 ISO965-1,
one plunged
See figure 3.
See figure 3
ouse-Hinds, S.A.
ouse-Hinds, S.A.
ouse-Hinds, S.A. catalogue
ouse-Hinds, S.A.
See wiring diagram.
6.
Maintenance
¡Observe the national rules applicable to
maintenance, servicing, inspection and
repairing of apparatus for explosive atmospheres,
as well as the general rules of engineering!
Servicing
¡The responsable of the safe use of these
apparatus is the property!
When servicing, in particular those components that
affect the explosion protection , will have to cheked,
e.g.:
Housing and glass for any cracks or damage.
The flameproof joint have to be clean,
undameged, without corrosion and perfect
greassed.
Gaskets for their perfect conditions.
Cable entries whitout corrosion.
Terminlas and blanking plugs for their firm fix.
Lamp replacement in acc. with the manufacturer
instructions.
Type of lamps used in acc. with the luminaire
specifications.
¡The flameproof of these apparatus have to
be greassed permanentlly in order to ensure
it protection in front of the corrosion, water
ingrees and seize-up problems. Cleaning rest of
greasse and corrosion no using sharp metallic
devices who can damage the surface of the joint,
and greasing they using apropiate greasse
thermically and chemically stable, like e.g.:
    
Molikote
BR2 plus.
¡When the housing need to be repeinted, pay
attention that the flameproof joints rest without
Traks of coating!
Inspection
¡The nationals regulations have to be
observed!
E.g. in Spain the inspections of the installations in
hazardous areas, have to be done by "qualified"
personnel in accordance with the Electrotechnical
Low Votage Regulation following the indications
stablished in IEC 60079-17.
¡When the inspections are in degree of
"Detailled" or "Closed", the luminaires have
to be disconnected from the main conection!
Repairing
¡The nationals regulations have to be
observed. The tasks of repairing have to be
made by "qualified" personnel!
¡The reparation of the sealed part between the
collarand the glass have to be done by
Cooper Cr
Cooper Crouse-Hinds, S.A.
Cooper Cr
Cooper Cr
Cooper Cr
ouse-Hinds, S.A.
ouse-Hinds, S.A.
ouse-Hinds, S.A.
ouse-Hinds, S.A..
The users are not authorized to repair this sealed
part!
¡All reparations have to be done without
voltage!
For repair electrical equipments in protection mode is
suggested follow the instructions indicated
in IEC 79-19.
¡Only use genuine Cooper Cr
Cooper Crouse-Hinds, S.A.
Cooper Cr
Cooper Cr
Cooper Cr
spare parts!
Subject to alteration or supplement of this product
without any advertisement before.
Cooper Crouse-Hinds, S.A.
ouse-Hinds, S.A.
ouse-Hinds, S.A.
ouse-Hinds, S.A.
ouse-Hinds, S.A.