between the two terminals (see Figure 4, page 4). A tog-
gle switch is provided with each HomeWorks 8 Series
Processor for this purpose. For maximum reliability, group
Module Interfaces on a single switch. This arrangement
should have the switch and all of the Module Interfaces
wired in parallel (see Figure 4, page 4).
Note: Proper polarity must be maintained across all
units. For manual override cable runs less than 1000
feet (300 m) that are connected to a single Module
Interface, 24–16 AWG (0.5–1.5 mm
used. For Manual Override cable runs exceeding 1000
feet (300 m) or those that are connected to multiple
Module Interfaces, 18–16 AWG (1.0–1.5 mm
must be used. If the installer chooses to use their own
switch, the switch must be rated for switching 50 mA
@ 28 V . For switching multiple Module Interfaces
the switch must be rated for switching the sum of the
current for all of the Module Interfaces connected (e.g.,
6 Module Interfaces wired to a single Manual Override
switch would require a switch rated for 300 mA @ 28
V ).
17. Program Manual Override Scene. The Manual Override
levels can be programmed using the HomeWorks
Illumination Software in the Load Schedule screen.
Figure 3 - HomeWorks 8 Series
Address Number and Switch Setting
TM
2
) wiring can be
2
) wiring
Processor Address Settings
TM
Example: Setting Switch #6 ON.
OFF - Left
ON - Right
Configuration DIP Switches
OFF
DIP Switch
Normal Mode
1
2
User-Configured
RS-232 Baud Rate
3-6
Address
ON
Boot Mode
9600 Baud
3