pump data plate values: Pmin 1 bar/ Pmax 3 bar
adjust the valve outlet to give a pressure of 3 bar < P1< 5 bar
- Example n°2.
Conditions:
open circuit, pressure P0 = 0 bar
pump data plate values: Pmin 1 bar/ Pmax 3 bar
adjust the valve outlet to give a pressure of 1 bar < P1 < 3 bar
c) Verify correct operation of the pump similarly under normal run-
ning conditions.
Check also that the amperage of the pump is within the limits indi-
cated on the data plate.
d) Switch off the chiller and proceed to top up the hydraulic circuit at
the "SET" temperature.
e) Check that the temperature of the "treated" water does not fall
below 5 °C and that the ambient temperature in which the hydraulic
circuit operates does not fall below 5 °C. If the temperature is too
low, add the appropriate quantity of glycol, as explained under head-
ing 3.4.2
4.3.2
Adjustments setpoint
M0
a-MAINTENANCE
Inlet water
00.08C
i-Input/Output
Outlet water
00.08C
k-clock
U1 ON
CH
s-Setpoint
a-MAINTENANCE
Summer
i-Input/Output
Setpoint
k-clock
Winter
s-Setpoint
Setpoint-------
Actual setpoint S0
Summer
Setpoint 00.008
00.08C°
Winter
Setpoint-------
English

4.4 Parameter settings

General
Th ere are two levels of protection for parameters:
a) Direct (D): with immediate access, User-changeable;
b) Password protected (U): password required for access; Factory-set
parameters.
4.4.1
Parameter Set point (Diretto)
PARAMETER
Summer setpoint
4.4.2
Chiller Parameters (User)
PARAMETER
Enter password.
Summer setpoint min. limit.
Summer setpoint max. limit.
Select adjustment probe.
Type of adjustment with evaporator
inlet probe.
Summer forced deactivation - outlet
adjustment.
Adjustment range.
Enable remote On/Off
Type of On. Remote Off from
S1
master.
yy.yyyy
Enable On/Off by supervisor.
Alarm relay logic.
Enable language screen at start-up.
Supervision network card identifi ca-
tion number.
Supervision network card commu-
S1
nication speed.
Select serial communication net-
work.
Select type of unit of measure.
Enter new password.
Screen
Master
Default
/Slave
S1
M/S
12.0
Screen
Master
Default
/Slave
P0
M/S
1234
P1
M/S
7.0
P1
M
17.0
P3
M
inlet
proportio-
P4
M
nal
P5
M
5.0
P6
M
3.0
Pa
M/S
N
Pa
M
on-off unità
Pl
M/S
N
Pl
M/S
N.A.
Pc
M/S
Pj
M/S
Pj
M/S
19200
Pj
M/S
modbus
Pm
M
Standard
Pk
M/S
Hyperchiller 450-760

4.5 Alarms management

CODE
Description
011
Serious Alarm
012
PhaseMonitor Alarm
031
Antifreeze Alarm
001
Unit 1 Offl ine
002
Unit 2 Offl ine
020
Compressor Th ermal Protection
015
Diff erential Oil Pressure Switch
032
Low Pressure Diff erential
017
Low pressure switch
016
High pressure switch
034
Low Transducer Pressure
033
High Transducer Pressure
021
Fan 1 Th ermal Protection
022
Fan 2 Th ermal Protection
035
High delivery temperature
053
Compressor Maintenance
060
B1 Probe Fault
061
B2 Probe Fault
062
B3 Probe Fault
063
B4 Probe Fault
064
B5 Probe Fault
065
B6 Probe Fault
066
B7 Probe Fault
S
067
B8 Probe Fault
1
041
32KB Clock Card Fault

4.6 Automatic restart

In the event of a power failure, when power is restored the chiller will
assume theOn-Off statusheld at themoment the power was lost.
-
RESET
Manual
Manual
Manual
Automatic
Automatic
Manual
Manual
Manual
Manual
Manual
Manual
Manual
Manual
Manual
Manual
Manual
Automatic
Automatic
Automatic
Automatic
Automatic
Automatic
Automatic
Automatic
Manual