Low mains
e37
 
voltage (LP)
High mains
 
e38
voltage (HP)
Critical over-
 
e32-e35
heating of
electronic parts
Protection
 
e39-e40
against
overcurrent
e21-e30
Voltage Error
 
Twin
communication
 
e31
absent
e42
Dry operation
 
Motor excess
e56
 
temperature
- Switch off system power.
- Wait for the warning lights on the control
panel to go off, then power the system
again.
- Check that the mains voltage is correct,
if necessary reset it at the plate values.
- Switch off system power.
- Wait for the warning lights on the control
panel to go off, then power the system
again.
- Check that the mains voltage is correct,
if necessary reset it at the plate values.
- Switch off system power.
- Wait for the warning lights on the control
panel to go off.
- Check that the system ventilation ducts
are not blocked and that the environ-
ment temperature of the premises is
correct.
- Check that the circulator turns freely.
- Check that any antifreeze added does
not exceed the maximum percentage
of 30%.
- Switch off system power.
- Wait for the warning lights on the control
panel to go off, then power the system
again.
- Check that the mains voltage is correct,
if necessary reset it at the plate values.
- Check that the twin communication ca-
ble is intact.
- Check that both circulators are pow-
ered.
- Put the system under pressure.
- Switch off system power.
- Wait for the motor to cool down
- Power the system again
f < 100 Hz
 
e57 ; e58
f > 5 kHz
Energy Efficiency Index - EEI
EVOPLUS 40/180 M
EVOPLUS 60/180 M
EVOPLUS 80/180 M
EVOPLUS 110/180 M
EVOPLUS 40/180 XM
EVOPLUS 60/180 XM
EVOPLUS 80/180 XM
EVOPLUS 110/180 XM
EVOPLUS B 40/220.32 M
EVOPLUS B 60/220.32 M
EVOPLUS B 80/220.32 M
EVOPLUS B 110/220.32 M
EVOPLUS B 40/250.40 M
EVOPLUS B 60/250.40 M
EVOPLUS B 80/250.40 M
EVOPLUS B 110/250.40 M
EVOPLUS D 40/220.32 M
EVOPLUS D 60/220.32 M
EVOPLUS D 80/220.32 M
EVOPLUS D 110/220.32 M
EVOPLUS D 40/250.40 M
EVOPLUS D 60/250.40 M
EVOPLUS D 80/250.40 M
EVOPLUS D 110/250.40 M
The benchmark for the most efficient circulators is EEI ≤ 0,20.
ENGLISH
Check that the PWM external signal is
operating and connected as specified.
0,23
0,22
0,22
0,22
0,21
0,21
0,21
0,21
0,22
0,22
0,22
0,22
0,21
0,21
0,21
0,21
0,23
0,23
0,23
0,23
0,22
0,22
0,22
0,22