4. Electrical work
SW1
ON
OFF
1 2 3 4 5 6 7 8 9 10
SW12
0
Fig. 4-4
4.4. Switch setting for high ceiling or at the time of
changing the number of air outlets
In this unit, the volume and speed of airfl ow can be adjusted by setting the switches
(SWA and SWB) on the indoor controller board.
PLFY-P32-P80VBM
SWA
SWB
Silent
4 direction
2.5 m
3 direction
2.7 m
2 direction
3.0 m
4.5. Sensing room temperature with the built-in sen-
sor in a remote controller
If you want to sense room temperature with the built-in sensor in a remote control-
ler, set SW1-1 on the control board to "ON". The setting of SW1-7 and SW1-8 as
necessary also makes it possible to adjust the air fl ow at a time when the heating
thermometer is OFF.

4.6. Types of control cables

1. Wiring transmission cables: Shielding wire CVVS or CPEVS
• Cable diameter : More than 1.25 mm
2. M-NET Remote control cables
Kind of remote control cable
More than 0.5 to 1.25 mm
Cable diameter
More than 0.5 to 1.25 mm
Remarks
When 10 m is exceeded, use cable with the
same specifi cations as transmission line wiring.
SWA
SWB
3
2
2
3
CN43
1
4
CN82
SW11
SW14
SWC
0
0
Standard
High ceiling
2.7 m
3.5 m
3.0 m
3.5 m
3.3 m
3.5 m
2
2
2
4.3. Setting addresses (Fig. 4-4)
(Be sure to operate with the main power turned OFF.)
• There are two types of rotary switch setting available: setting addresses 1 to 9
and over 10, and setting branch numbers.
Address board
PLFY-P100,P125VBM
SWA
SWB
Silent
4 direction
2.7 m
3 direction
3.0 m
2 direction
3.3 m
3. MA Remote control cables
Kind of remote control cable
2-core cable (unshielded)
Cable diameter
0.3 to 1.25 mm
Standard
High ceiling
3.2 m
4.5 m
3.6 m
4.5 m
4.0 m
4.5 m
2
7