ASSEMBLING THE BURNER

The assembly of the burner to the door of the boiler must
ensure perfect tightness to the products of combustion. Once
having installed the burner on the boiler, the space between
the burner draught tube and the refractory material on the
door must be filled with the layer of ceramic fibre (A) supplied.
This prevents the door from overheating and consequently
from being irreversibly deformed. The fuel connections to the
burner must be located so as to allow the complete opening
of the boiler door with the burner installed.
ASSEMBLING THE BURNER
MEGA
Lmin
(mm)
92 - 152
190 - 350 - 399
469 - 600
720 - 1060
1250 - 1480
1890
2360
3000 - 3600
CONNECTING THE FLAME
INSPECTION WINDOW
The flame inspection window features a pressure fitting (1) to be
connected via a silicone hose or copper pipe to the outlet on the
burner (2). This operation allows the air blown by the fan to cool
the glass and prevent it from turning black. Failure to connect
the hose or pipe to the window may cause the glass to break.
Lmax
S
(mm)
(mm)
230
300
172
250
320
192
290
360
218
320
390
239
320
390
248
340
410
262
340
470
262
350
480
272