Troubleshooting (Check Point) - Toshiba RAS-B10J2FVG-E El Manual Del Propietario

Ocultar thumbs Ver también para RAS-B10J2FVG-E:
Tabla de contenido

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

  • MEXICANO, página 34
Temp.
Outdoor Temperature
Operation
Heating
-15°C ~ 24°C
Cooling
-15°C ~ 46°C
Dry
-15°C ~ 46°C
w
Concerning multiple connections, please inquire to the dealership or refer
to the catalog.
17

TROUBLESHOOTING (CHECK POINT)

The unit does not operate.
• The power main switch is
turned off.
• The circuit breaker is activated
to cut off the power supply.
• Stoppage of electric current.
• ON timer is set.
Note: When there is an abnormality in the product, abnormal code
(2 digits) will be displayed on the unit display panel. Please contact
the dealership.
In case of multiple connection
• Check whether the operation mode is different from what has been selected
for the units in the other rooms (The following combinations of operations
cannot be performed: COOL and HEAT, DRY and HEAT).
• Select the same operation mode as for the other rooms.
18
REMOTE CONTROL A-B SELECTION
To separate using of remote control for each indoor unit in case of 2 air
conditioners are installed near.
Remote Control B Setup.
1. Push and hold
button on the Remote Control by the tip of the
CHECK
pencil. "00" will be shown on the display. (Picture 1)
2. Press
during pushing
will disappear and the air conditioner will turn OFF. The Remote Control
B is memorized. (Picture 2)
Note: 1. Repeat above step to reset Remote Control to be A.
2. Remote Control A has not "A" display.
3. Default setting of Remote Control from factory is A.
1
Unit B setup.
Press and hold MODE button for more than 20 seconds.
When A setup changed to B setup : 5 beeps will sound and operation lamp
blinks for 5 seconds.
When B setup changed to A setup : 5 beep will sound.
ADJUSTING BRIGHTNESS OF UNIT
19
DISPLAY PANEL
1. Press and hold AIR OUTLET SELECT button then press MODE button
for 3 times (All lamp of the unit display panel will be switched on). (At that
time, please press and hold the AIR OUTLET SELECT button)
2. Press and hold AIR OUTLET SELECT button on Unit display panel,
then press TEMPERATURE button (Up), (Down) for select the desired
brightness.
3. Brightness will be settled when AIR OUTLET SELECT button is released.
Although the temperature indicator is switched off, if press the temperature
button (up) and (down), the set temperature will be indicated, and then can
adjust the temperature.
10 seconds after stopped pressing the button, the temperature indication
will be switched off.
4 stages of brightness can be changed.
Temperature indicator
1
Usual
2
Darkness
3
Turn off
4
Turn off
Room Temperature
Less than 28°C
21°C ~ 32°C
21°C ~ 32°C
Cooling or Heating is abnormally low
• The fi lters are blocked with dust.
• The temperature has been set
improperly.
• The windows or doors are opened.
• The air inlet or outlet of the outdoor
unit is blocked.
• The fan speed is too low.
• The operation mode is DRY.
• POWER SELECTION function is
set 75% or 50% (This function is
depend on remote controller).
. "B" will show on the display and "00"
CHECK
B
2
Other lamp
Usual
Darkness
Darkness
Turn off
CHANGE AIR OUTLET GRILLE ON
20
STABLE TIME (COOLING ONLY)
On cooling operation, whichever air outlet is set, only Upper is used when the
room temperature approaches the set temperature.
In case to keep up/down blowing, operate as below;
Press and hold AIR OUTLET SELECT button for more than 10 seconds (less
than 20 seconds) (4 beeps will sound then "1" indication at TEMPERATURE
indicator will light up for 5 seconds).
For return to the former status, press and hold AIR OUTLET SELECT button
for more than 10 seconds once again (In this time, 4 beeps will sound then "0"
indication at TEMPERATURE indicator will blinks for 5 seconds).
21
AIR INLET GRILLE MAINTENANCE
Wash the air inlet grille with water using the soft sponge or towel.
• Dry it well in a shadow area after washing.
• Scour heavy dirt with neutral detergent for kitchen, and rinse it with the
water (Do not use the wire wool).
• Do not press the front panel strongly. It may be cracked.
POWER-SELECTION AND SILENT
22
OPERATION (OUTDOOR UNIT)
Power-Selection (
)
This function is used when the circuit breaker is shared with other electrical
appliances. It limits the maximum current and power consumption to 100%,
75%, or 50% and can be implemented by POWER-SELECTION. The lower
percentage, the higher saving and also longer compressor lifetime.
Note:
• When the level is selected, POWER-SEL level fl ashes on remote LCD
display for 3 seconds.
In case of 75% and 50% level, number "75" or "50" also fl ashes for 2
seconds.
• Due to the reason that POWER-SELECTION function limits the
maximum current, inadequate cooling or heating capacity may occur.
Silent Operation (
)
Keep outdoor unit operating silently to ensure either yourself or neighborhood
will have a tight sleep in nighttime. By this feature, the heating capacity will
be optimized to deliver such silent experience. The silent operation can be
selected from one of two purposes (Silent 1 and Silent 2).
There are three setting parameters: Standard level > Silent 1 > Silent 2
Silent 1:
Though operating silently, the Heating (or Cooling) capacity is still prioritized to
ensure having suffi cient comfort inside the room.
This setting is a perfect balance between the Heating (or Cooling) capacity
and the Sound level of outdoor unit.
Silent 2:
Compromising the Heating (or Cooling) capacity to the Sound level in any
circumstance where the outdoor unit's sound level is highly prioritized.
This setting has a purpose to reduce the maximum sound level of outdoor unit
by 4 dB(A).
Note:
• While activating of Silent operation, inadequate heating (or cooling)
capacity may occur.
Power-Selection and Silent Operation (Outdoor Unit)
[100%]
[75%]
[50%]
SILENT#2
SILENT#1

Publicidad

Tabla de contenido
loading

Tabla de contenido