TBML 120 MC - 160 MC - 200 MC PIPE SIZING DIAGRAMS
1 Tank
3 Wire-net filter
4 Pump
6 Suction pipe
7 Return pipe
10 Foot valve
GRAVITY SUPPLY SYSTEM
1 Tank
2 Feeding pipe
3 Wire-net filter
4 Pump
5 Degasifier
PUMP AXIS
DROP-TYPE SYSTEM WITH SUPPLY FROM THE TANK TOP
1 Tank
3 Wire-net filter
4 Pump
6 Suction pipe
7 Return pipe
PUMP AXIS
INTAKE SUPPLY SYSTEM
PUMP AXIS
NOTE:
H = Difference in level between level in the tank and the pump axis.
L = Total pipeline length including the vertical length.
Deduct 0.25 m for each elbow or gate.
0006160035_201408
6 Suction pipe
7 Burner return pipe
8 Automatic interception device
with burner off
9 One-way valve
8 Automatic fuel interception device at
burner shut off
9 Non-return valve
10 Foot valve
H
meters
0.5
1
1.5
2
2.5
3
3.5
For any components missing in the pipes, comply with current
regulations.
13 / 36
H
Gesamte L.
Meter
Meter
Ø i. 16 mm.
1
40
1.5
45
2
45
2.5
50
3
50
H
Gesamte L.
Meter
Meter
Ø i. 16 mm.
1
40
1.5
45
2
45
2.5
50
3
50
Maßzahl T = 3.5 m. (max.)
L total metres
Ø i. 14 mm.
Ø i. 16 mm.
36
55
30
48
25
41
20
32
15
24
10
15
4
7.5