3.5KW Generator
Installation (cont'd)
Support and Mounting
Mount the generator on a concrete slab capable of supporting the weight of
the generator. The slab must extend on all sides beyond the frame by at
least one foot. Contact a cement contractor for slab specifications if
necessary. Attach the frame to the concrete slab using 3/8" diameter
expansion anchor bolts (not supplied).
Grounding
Note: It is recommended that only a trained and licensed
electrician perform this procedure.
Connect a #6 AWG grounding wire (not included) from the ground
connector (8) on the generator to a grounding rod (not included) that has
been driven at least 24 inches deep into the earth. The grounding rod must
be an earth-driven copper or brass rod (electrode) which can adequately
ground the generator.