4.4

Connecting thermostats

1. Ensure that the conditions for the auto-linking function are
met when connecting the thermostats. See section
linking, page
5.
2. In each thermostat, connect the cable to the controller to the
connector labelled Power.
In Uponor Thermostat T-34, connect to the only connector.
3. In Uponor Controller, connect one wire of the thermostat
cable to position 1 and the other wire to position 2, 3, or 4.
See table below and wiring diagram in section
NOTE!
The two wires from the thermostat are non-polarized.
Pos. Label Heating
1
Common terminal
2
No timer control
3*
Z1
Timer control zone 1 Timer control
4*
Z2
Timer control zone 2 No cooling for this room
* = C-35 only
4. If an optional floor sensor or remote sensor is used, connect
the cable to the connector labelled EXT. See illustrations
above.
6
4.2 Auto-
4.1, page
5.
Cooling*
Common terminal
No timer control
5. (T-33 only) Adjust the room temperature setpoint with the
potentiometer labelled ROOM.
6. (T-33 and T-37 only) Adjust the optional floor sensor for
either a maximum temperature or a minimum temperature
with the potentiometer labelled FLOOR.
NOTE!
All Uponor thermostats are frost protected with
minimum temperature +5 degrees.
4.5
Connecting Uponor Timer I-36 (C-35
only)
To connect a timer to the controller:
1. Connect the timer to positions 1 and 2,
See wiring diagram in section
4.6
Connecting a heating–cooling switch (C-
35 only)
If the installation is equipped with a cooling unit, the Uponor
Control System Wired mode can be switched with a heating–
cooling relay.
1. Connect the heating–cooling switch to positions 11 and 12,
.
See wiring diagram in section
4.7
Connecting a dew-point sensor (C-35
only)
If the installation is equipped with a dew-point sensor, the
Uponor Control System Wired will close the actuators for all zones
when the dew point is reach.
1. Connect the dew-point module switch to positions 4 and 5.
2. Connect the dew-point module power to positions 6 and 7.
See wiring diagram in section
4.8

Connecting a circulation pump

The pump output is switched on when at least one actuator is
open.
1. Connect the circulation pump to connectors labelled PUMP.
See wiring diagram in section
NOTE!
There is no power in the controller to supply the
pump. The pump connector in the controller provides
only a dry contact to switch off and on the power
connection to the pump.
4.9

Connecting a boiler relay

In heating mode, the boiler output is switched on when at least
one actuator is open, that is a heat demand exists in at least one
zone.
1. Connect the boiler relay to connectors labelled BOILER.
See wiring diagram in section
NOTE!
Check the boiler manufacturer's instructions before
connecting the boiler relay.
UPONOR CONTROL SYSTEM WIRED - QUICK GUIDE
.