Technical Data
Input
• Nominal voltage:
380-480 VAC 3PH auto select
• Power factor (PFC):
as required to meet EN61000-3-2
Output
• Nominal voltage:
24V (22.5-28.5VDC Adj.)
• Power boost:
1.5x nominal current for 2 sec.
• Holdup time:
> 15ms at Full Load (25˚C)
• Tolerance:
< ±2 % overall
Line regulation
<0.5%
Load regulation
<0.5%
Time & temp. drift
<1%
• Initial voltage setting:
24.5V ± 1%
• Ripple:
< 50mVpp
• Power back immunity:
> 35V
• Parallel Operation:
Switch Selectable
• Over voltage protection:
< 33VDC
Standards, Certifications
EMC
Emissions
EN 61000-6-3, Class B EN55011, EN55022 Radiated Conducted
including Annex A
Immunity
EN 61000-6-2, EN61000-4-2 Level 4, EN61000-4-3 Level 3,
EN61000-4-6 Level 3, EN61000-4-4 Level 4 input and level 3 output.
EN61000-4-5 Isolation class 4, EN61000-4-11,Transient protection
according to VDE 0160/W2 over entire load range.
Approvals
EN60950, UL508 Listed, cULus, UL 60950, cURus, CE (LVD 73/23 &
93/68/EEC), (EMC 89/336 & 93/68/EEC). EN61000-3-2, EN60079-15
(Class 1, Division 2 hazardous location, Groups A, B, C, D w/ T3 temp
class up to 60˚C Ambient.) SEMIF47 Sag Immunity.
Environmental Data
Ambient temperature
• Storage/Shipment
-25˚C...+85˚C
• Full nominal load
-10˚C...+60˚C
• Derated
+60˚C...+70˚C
Degree of protection:
IP20 (EN60529), Protect the unit from moisture
(and condensation)
Installation
Fusing
Input
Internally fused.
Output
Outputs are capable of providing high currents for short
periods of time for inductive load startup
or switching.
Mounting
Simple snap-on to DIN TS35/7.5 or TS35/15 rail system.
Unit should handle normal shock and vibration of industrial
use and transportation without falling off the rail.
Connections
Input: screw terminals, connector size range: 16-10AWG
(1.5-6mm2) for solid conductors.
Output: One terminal per output, connector size range:
16-5AWG(1.5-16mm2) for solid conductors.
This equipment is suitable for use in Class 1, Division 2, Groups A,B,C,D or
non-hazardous locations only
WARNING – EXPLOSION HAZARD – Substitution of components may impair
suitability for Class 1, Division 2.
WARNING – EXPLOSION HAZARD – Do not disconnect equipment unless power
has been switched off or the area is known to be non-hazardous.
DIN Rail Mounting
Montaje en Riel DIN
Snap on the DIN Rail:
Atorar en en Riel DIN:
1. Tilt unit as illustrated
1. Incline la unidad como
se ilustra
2. Put it onto the DIN Rail
2. Póngala sobre el Riel
3. Push downwards until
DIN
stopped
3. Empuje hacia abajo
4. Push at the lower front
hasta que se detenga
edge to lock
4. Empuje de la parte
5. Shake the unit slightly
baja del frente para
to ensure that the unit
asegurar
is secure
5. Mueva la unidad lig-
eramente para verificar
está segura
SDN Series
Power Supplies
Technical Services
USA
International
SDN 40-24-480
E-Mail
tech@sola-hevi-duty.com
www.solaheviduty.com
Montage du Rail DIN
Poser le Rail DIN:
1. Incliner l'appareil
comme illustré
2. Encliqueter sur le
Rail DIN
3. Pousser vers le bas
jusqu'à l'arrêt
4. Appuyer sur le bord
inférieur pour fixer
5. Vérifier que l'appareil
est bien fixé
(800) 377-4384
(847) 268-6000
P/N: A272-105
Rev. 1 (January 2006)