8 Configuración
8.3
Ajustes para todas las configuraciones
Ajuste 17(27)-4: Primero seleccione la velocidad del ventilador.
Establézcala en alta o muy alta.
Direct duct connection
or external fan
Setting 19(29)-2 and setting
19(29)-3: Balance return air
and outdoor air with fan steps
1-15, based on the air flow
curves (see the databook) and
the system pressure drop.
You MUST activate setting
19(29)-0-03.
Warning: If it is NOT activated,
the clean filter signal will NOT
be given at the correct time.
Guía de referencia para el instalador y el usuario
32
All other system configurations
VAM350~1000
Choose between 19(29)-0-04 or 19(29)-0-05
Setting 19(29)-2 and setting
19(29)-3: Balance return air
and outdoor air with fan steps
1-15, based on the air flow
curves (see the databook) and
the system pressure drop.
You can activate setting
19(29)-0-04.
Warning: If it is NOT activated,
the clean filter signal will NOT
be given at the correct time.
VAM1500+2000
Warning: The ducting
pressure drop of the top
and bottom units has to be
equal to have a balanced
system.
You can activate setting
19(29)-0-05: the nominal
point is automatically
determined at the nominal
flow rate (see the databook
for specific values).
Unidad de ventilación con recuperación de calor
VAM350~2000J7VEB