Installation
9.1.3 NEC and UL Compliance
Fuses or circuit breakers are mandatory to comply with NEC 2009. We recommend using a selection of the following.
The fuses below are suitable for use on a circuit capable of delivering 100,000 Arms (symmetrical), 240V, or 480V, or 600V
depending on the drive voltage rating. With the proper fusing, the drive Short Circuit Current Rating (SCCR) is 100,000 Arms.
AF-650 GP
Bussmann
Power
1)
[kW] / [HP]
Type RK1
0.25–0.37 /
KTN-R-05
0.33–0.5
0.75 / 1
KTN-R-10
1.5 / 2
KTN-R-15
2.2 / 3
KTN-R-20
3.7 / 5
KTN-R-30
5.5 / 7.5
KTN-R-50
7.5 / 10
KTN-R-60
11 / 15
KTN-R-80
15–18.5 /
KTN-R-125
20–25
22 / 30
KTN-R-150
30 / 40
KTN-R-200
37 / 50
KTN-R-250
Table 9.8 200–240V
AF-650 GP
SIBA
Power
[kW] / [HP]
Type RK1
0.25-0.37 /
5017906-005
0.33-0.5
0.75 / 1
5017906-010
1.5 / 2
5017906-016
2.2 / 3
5017906-020
3.7 / 5
5012406-032
5.5 / 7.5
5014006-050
7.5 / 10
5014006-063
11 / 15
5014006-080
15/18.5 /
2028220-125
20-25
22 / 30
2028220-150
30 / 40
2028220-200
37 / 50
2028220-250
Table 9.9 200–240V
AF-650 GP Quick Guide
Recommended max. fuse
Bussmann
Bussmann
Type J
Type T
JKS-05
JJN-05
JKS-10
JJN-10
JKS-15
JJN-15
JKS-20
JJN-20
JKS-30
JJN-30
KS-50
JJN-50
JKS-60
JJN-60
JKS-80
JJN-80
JKS-125
JJN-125
JKS-150
JJN-150
JKS-200
JJN-200
JKS-250
JJN-250
Recommended max. fuse
Littel fuse
Type RK1
KLN-R-05
KLN-R-10
KLN-R-15
KLN-R-20
KLN-R-30
KLN-R-50
KLN-R-60
KLN-R-80
KLN-R-125
KLN-R-150
KLN-R-200
KLN-R-250
DET-759A
Bussmann
Bussmann
Type CC
Type CC
FNQ-R-5
KTK-R-5
FNQ-R-10
KTK-R-10
FNQ-R-15
KTK-R-15
FNQ-R-20
KTK-R-20
FNQ-R-30
KTK-R-30
-
-
-
-
-
-
-
-
-
-
-
-
-
-
Ferraz-
Shawmut
Type CC
ATM-R-05
ATM-R-10
ATM-R-15
ATM-R-20
ATM-R-30
-
-
-
-
-
-
-
Bussmann
Type CC
LP-CC-5
LP-CC-10
LP-CC-15
LP-CC-20
LP-CC-30
-
-
-
-
-
-
9
-
Ferraz-
Shawmut
3)
Type RK1
A2K-05-R
A2K-10-R
A2K-15-R
A2K-20-R
A2K-30-R
A2K-50-R
A2K-60-R
A2K-80-R
A2K-125-R
A2K-150-R
A2K-200-R
A2K-250-R
43
9