Audible Alarm
Using the up and down arrow keys (), choose either ON or OFF.
When the audible alarm is ON, choose between latch or unlatch. When
latched, the audible alarm will remain on if an alarm condition had
existed and then returned to normal operating conditions. When
unlatched, the audible alarm will only remain on while an alarm
condition exists.
•
®
C
ERTIFIER
Using the up and down arrow keys (), choose ON or OFF. This
option should always be set to OFF unless you are using the TSI
®
C
Air Velocity Calibrator. When ON is selected you can set
ERTIFIER
the measurement units as feet/min (FEEt) or m/s (Si) using the up and
down arrow keys (), and then set a density correction factor using
the up and down arrow keys (). For a more detailed explanation see
section titled "More Detail on the C
Option".
Setup Message
FULL ScALE =
inPUt =
ZErO
SPAn
LO AL =
Hi AL =
LEdS
rELAy
Aud
cErti
UnitS
Fact
PLAtE
Full scale value: 0.1000 to 99990
Input signal: 0-5 VDC, 0-10 VDC, 1-5 VDC,
2-10 VDC, 0-20 mA, 4-20 mA
Zero adjust: ±1% of selected full scale value
Span adjust: 0.100 to 1.900
Low alarm: between -1 and full scale
High alarm: between 0 and full scale
LEDs: latched or unlatched
Relays: latched or unlatched
Audible alarm: on or off
When on, choose between latched and unlatched
®
C
function: on or off
ERTIFIER
FEEt (feet/minute) or Si (meters/second)
Density correction factor: 0.1000 to 1.9000
Plate choices: nOnE, 1, 2, tiny
®
Air Velocity Calibrator
ERTIFIER
Available settings
9