Only one remote control means (panel or switch) can be connected to the system. That means only one GX.
9.5.7 Three-phase operation
The product can also be used in 3-phase wye (Y) configuration. To this end, a connection between the devices is made
by means of standard RJ45 UTP cables (the same as for parallel operation). The system will require subsequent
configuration.
Pre-requisites: see Section Voltage Sense
1.
Note: the product is not suitable for 3-phase delta (Δ) configuration.
2.
When the AS4777.2 grid code has been selected in VEConfigure, only 2 units in parallel per phase are allowed
in a three phase system.
For full details on parallel and three-phase configuration always discuss with your Victron distributor first and please see
this specific manual:
https://www.victronenergy.com/live/ve.bus:manual_parallel_and_three_phase_systems
9.5.8 Connection to the VRM Portal
Connection of the product to VRM requires an internet connection. This can be made via wifi, or preferably a hardwired
ethernet cable to an internet connected router.
The VRM site id is located on a sticker inside the cable connections area of the device.
For more information to set up VRM, refer to the
10. Configuration
This section is intended mainly for stand-alone applications
For grid connected Energy Storage Systems (ESS) please see
•
Settings may only be changed by a suitable qualified installer with the appropriate training, and subject to local
requirements. Please contact Victron for further information or necessary training.
•
Read the instructions thoroughly before implementing changes.
•
During setting of the charger, the AC input must be removed.
10.1 Standard settings: ready for use
On delivery, the product is set to standard factory values. In general, these settings are suitable for single-unit operation.
WARNING
Possibly, the standard battery charging voltage is not suitable for your batteries! Refer to the manufacturer's
documentation, or to your battery supplier!
Standard factory settings
Setting
Inverter frequency
Input frequency range
Input voltage range
Inverter voltage
Stand-alone / parallel / 3-phase
AES (Automatic Economy Switch)
Ground relay
Charger on / off
Battery charge curve
Charging current
Battery type
Automatic equalisation charging
Absorption voltage
Absorption time
VRM Getting Started Manua
https://www.victronenergy.com/live/ess:start
Value
50 Hz
45 – 65 Hz
180 – 265 VAC
230 VAC
stand-alone
four-stage adaptive with BatterySafe mode
100% of the maximum charging current
Victron Gel Deep Discharge (also suitable for Victron AGM Deep
Discharge)
57.6V
up to 8 hours (depending on bulk time)
off
On
on
off