DIP switches ds2 and ds1 are reserved for the selection of stand-alone, parallel or 3-phase operation
Stand-alone operation
Step 1: Setting ds2 and ds1 for stand-alone operation
DS-8 AC-in-1
Set as desired
DS-7 AC-in-1
Set as desired
DS-6 AC-in-1
Set as desired
DS-5 AC-in-2
Set as desired
DS-4 Charging current Set as desired
DS-3 Charging current Set as desired
DS-2 Stand-alone operation
DS-1 Stand-alone operation
Examples of DIP switch settings for stand-alone mode are given below.
Example 1 shows the factory setting (since factory settings are entered by computer, all DIP switches of a new product are set
to 'off'.
Important: When a panel is connected, the AC-in-2 current limit is determined by the panel and not by the value stored in the
Quattro.
Four examples of stand-alone settings:
DS-8 AC-in-1
on
DS-7 AC-in-1
on
DS-6 AC-in-1
off
DS-5 AC-in-2
off
DS-4 Charging current
on
DS-3 Charging current
off
DS-2 Stand-alone mode
off
DS-1 Stand-alone mode
off
Step1, stand-alone
Example 1 (factory setting):
8, 7, 6 AC-in-1: 30A
5 AC-in-2: 16A
4, 3 Charging current: 75%
2, 1 Stand-alone mode
To store the settings after the required values have been set: press the 'Up' button for 2 seconds (upper button to the right of
the DIP switches, see appendix A, position K). The overload and low-battery LEDs will flash to indicate acceptance of the
settings.
We recommend making a note of the settings, and filing this information in a safe place.
You can now re-use the DIP switches to apply the remaining settings (step 2).
16
off
off
DS-8
on
DS-8
DS-7
on
DS-7
DS-6
off
DS-6
DS-5
off
DS-5
DS-4
on
DS-4
DS-3
on
DS-3
DS-2
off
DS-2
DS-1
off
DS-1
Step1, stand-alone
Step1, stand-alone
Example 2:
Example 3:
8, 7, 6 AC-in-1: 30A
8, 7, 6 AC-in-1: 16A
5 AC-in-2: 16A
5 AC-in-2: 16A
4, 3 Charge: 100%
4, 3 Charge: 100%
2, 1 Stand-alone
2, 1 Stand-alone
off
DS-8
on
on
DS-7
off
on
DS-6
on
off
DS-5
on
on
DS-4
off
on
DS-3
on
off
DS-2
off
off
DS-1
off
Step1, stand-alone
Example 4:
8, 7, 6 AC-in-1: 25A
5 AC-in-2: 30A
4, 3 Charge: 50%
2, 1 Stand-alone