The values or options in the screen displays shown must be entered before start-up.
TIMER VALUES
AT START CAPACITY DECREASE
CAPACITY INCREASE MOTOR ON
CAPACITY DECREASE MOTOR ON
CMP STARTER AUX CONTACT BYPASS
CAP INCREASE MOTOR OFF
CAP DECREASE MOTOR OFF
VOL SLIDE ADJ TIMER
MINIMUM CAP PRELUB TIME
RUN CYCLE OIL PRESS BYPASS
PRELUB PUMP TIME LIMIT
CAPACITY HOLD MOTOR OFF TIME
CAPACITY HOLD MOTOR ON TIME
FLTR DIFF PR SAFETY CHANGEOVER
LO OIL SEP LEVEL BYPASS TIMER
AUTO RESTART AFTER POWER FAIL
OIL SEP TEMP SAFETY CHANGEOVER
LO OIL INJ TEMP SFTY CHANGEOVER
ANTIRECYCLE STRT TIMER (MIN)
START LAG COMP TIMER (MIN)
STOP LAG COMP TIMER (MIN)
FORCE START LAG COMP (MIN)
HOT STRTS/HR COUNTER (COUNTS)
NOTES:
(1)
Must be field set.
(2)
Set only if Lead/Lag option is selected.
VISSION MICRO-CONTROLLER
MANUAL DE OPERACIONES
TABLE 4.
SYSTEM TIMER VALUES WORKSHEET
(1)
(2)
(2)
(2)
(1)
SYSTEM VALUES
- 51 -
VALUE LIMITS
DEFAULT VALUES
0/999 SEC
0/255 SEC
0/255 SEC
0/255 SEC
0/255 SEC
0/255 SEC
0/255 SEC
0/255 SEC
0/90 SEC
0/255 SEC
0/255 SEC
0/255 SEC
0/999 SEC
0/120 SEC
1/240 MIN
0/15 MIN
0/15 MIN
0/30 MIN
0/30 MIN
0/30 MIN
0/60 MIN
1/10 COUNTS
ORIGINAL ISSUE
15 SEC
3 SEC
3 SEC
10 SEC
20 SEC
20 SEC
20 SEC
5 SEC
60 SEC
15 SEC
10 SEC
2 SEC
60 SEC
60 SEC
5 MIN
5 MIN
6 MIN
20 MIN
5 MIN
5 MIN
30 MIN
3 COUNTS
3/03