Hazardous (Classified) Location
Class I, II, III, Division 1, Groups A,B,C,D,E,F,G
3)
Ui = 25V, Ii = 0.16A
Pi = 2W
Li = 0, Ci = 0
Minebea Intec
Load Cell Series PR62..
Hazardous (Classified) Location
Class I, II, III, Division 2, Groups A,B,C,D,E,F,G
3)
Vmax = 25V
Minebea Intec
Load Cell Series PR62..
Notes
1) In the USA: The installation must be in accordance with the National Electrical Code
ANSI / ISA-RP 12.06.01.
In Canada: The installation must be in accordance with the Canadian Electrical Code
2) The apparatus must not be connected to any device that uses or generates in excess of 250Vrms or DC.
U
= 250V.
m
3) In the USA: The Apparatus must be connected to a suitable ground electrode per National Electrical Code
NFPA 70, Article 504. The resistance of the ground pad must be less than 1 ohm.
In Canada: The Apparatus must be connected to a suitable ground electrode per Canadian Electrical Code
Part 1. The resistance of the ground pad must be less than 1 ohm.
The load cell ground (housing) must be insulated from the surface on which it is mounted or be at the same
potential of the NRTL approved apparatus ground as per installation drawings.
4)
apparatus.
5) The Entity Concept allows interconnection of intrinsically safe apparatus with associated apparatus not
specifically examined in combination as a system when the approved values of Vo and Io of the associated
apparatus are less than or equal to Vi and Ii of the intrinsically safe apparatus and the approved values of Co
and Lo of the associated apparatus are greater than Ci and Li of the intrinsically safe apparatus plus all cable
parameters.
7) Ambient temperature range:
-40°C .... +55°C (-40°F .... +131°F) for T5 and -40°C .... +70°C (-40°F .... +158°F) for T4A.
8) WARNING:
AVERTISSEMENT: LA SUBSTITUTION DE COMPOSANTS PEUT COMPROMETTRE LA SÉCURITÉ
SUBSTITUTION OF COMPONENTS MAY IMPAIR INTRINSIC SAFETY.
INTRINSÈQUE.
Material
Ausgabe / Revision
Änderung / Alteration
04
PA50180542
FM Approved Apparatus (USA) or
product is suitably certified for use
in Canada with Entity Concept
4)
parameters (see note 5) (Vo, Io,
Co, Lo) appropriate for connection
to intrinsically safe apparatus with
Entity Concept parameters
FM Approved Apparatus (USA) or
product is suitably certified for use
4)
in Canada with nonincendive field
wiring and output voltage of
25Vmax to the load cells.
of the NRTL approved
Benennung / Title
Zeichnungs-Nr. / Drawing number
4012 101 5688
2)
3)
2)
3)
®
, NFPA 70 and
®
, Part 1.
®
,
®
,
Maßstab /
Scale
1:1
Blatt
Sheet
Teildok. Nr./
592
von
Part doc. no.
of
1
1