b. This equipment shall be located in the same immediate area (such as, adjacent
c. The DC supply source is to be located within the same premises as this equipment.
d. There shall be no switching or disconnection devices in the grounded circuit
Restricted access locations
1675 LambdaUnite MSS systems contain optical circuit packs that can emit laser
radiation assessed as IEC Hazard Level 1M.
Therefore, 1675 LambdaUnite MSS systems may only be installed in restricted access
locations! Restricted access locations are controlled environments where there is no
ready access to the general public, but only to authorized persons who have received
adequate training in laser safety.
............................................................................................................................................................................................................................................................
1675 LU MSS
365-374-159R11.01.28 Release 11.01.28
Issue 1 November 2012
cabinets) as any other equipment that has a connection between the grounded
conductor of the same DC supply circuit and the grounding conductor, and also the
point of grounding of the DC system. The DC system shall not be grounded
elsewhere.
conductor between the DC source and the point of connection of the grounding
electrode conductor.
CAUTION
Laser hazard
1 - 9