Soft Starter Selection - Siemens SIKOSTART 3RW34 Instructions De Service

Tabla de contenido

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

  • MEXICANO, página 119

Soft Starter Selection

9
Soft Starter Selection
Each soft starter has two ratings: "In Line" and "Inside Delta."
Inside Delta ratings are higher than In Line ratings.
Be sure to select equipment with the proper ratings for the type of connections used.
For 24 V DC control voltage replace the "?" in the order number with "2".
For 115 V AC control voltagereplace the "?" in the order number with "3".
For 230 V AC control voltage replace the "?" in the order number with "4".
Decisive for the rating of the motor control unit is the rated operational current I
The kW values specified serve as indicators for the rated power of three-phase motors and are based on the
relevant series of standards.
U
: Rated operating voltage
e
I
: Rated operational current
e
Order Number
3RW34 54-0DC?4
3RW34 55-0DC?4
3RW34 57-0DC?4
3RW34 58-0DC?4
3RW34 65-0DC?4
3RW34 66-0DC?4
3RW34 67-0DC?4
3RW34 68-0DC?4
3RW34 83-0DC?4
3RW34 84-0DC?4
3RW34 86-0DC?4
3RW34 54-0DC?5
3RW34 55-0DC?5
3RW34 57-0DC?5
3RW34 58-0DC?5
3RW34 65-0DC?5
3RW34 66-0DC?5
3RW34 67-0DC?5
3RW34 68-0DC?5
3RW34 83-0DC?5
3RW34 84-0DC?5
3RW34 86-0DC?5
Table 10 : Motor Power Ratings (kW) TA = 40°C and 50 Hz
26
In Line
U
in V
230 V
400 V
e
I
in A
e
kW
kW
200
57
15
30
to
70
18,5
37
460
110
30
55
135
37
75
162
45
90
195
55
110
235
75
132
352
110
200
500
160
250
700
200
400
1050
315
560
400
57
30
to
70
37
600
110
55
135
75
162
90
195
110
235
132
352
200
500
250
700
400
1050
630
Inside Delta
U
in V
500 V
230 V
e
I
in A
e
kW
kW
200
99
30
to
121
37
400
191
55
234
75
281
90
338
110
407
132
610
200
866
250
1212
400
1819
530
37
400
99
to
45
121
600
75
191
90
234
110
281
132
338
160
407
250
610
355
866
500
1212
710
1819
3ZX1012-0RW34-1AN1
.
e
400 V
500 V
kW
kW
55
55
110
132
160
200
250
355
500
710
1000
55
55
55
75
110
132
132
160
160
200
200
250
250
315
355
400
500
630
710
850
1000
1200

Publicidad

Tabla de contenido
loading

Tabla de contenido