No: 24054 – 09/16 rev. 1
Catalog Numbers • Les Numéros de Catalogue • Números de Catálogo: CI-305, CI-305-1
Country of Origin: Made in China • Pays d'origine: Fabriqué en Chine • País de origen: Hecho en China
The Wattstopper CI-305 360° passive infrared (PIR) occupancy sensors turn lighting systems on and off based on occupancy.
The sensors can be configured to turn lighting on, and hold it on as long as the sensor detects occupancy. After no movement is
detected for a user specified time (30 seconds to 30 minutes) the lights are switched off. A "walk-through" mode can turn lights off after
only 3 minutes, if no activity is detected after 30 seconds of an occupancy detection.
The CI-305 operates on 24V supplied by Wattstopper Power Packs, 24VAC or half wave rectified AC.
Depending upon obstacles such as furniture or partitions, the area of coverage may be less or more
than the sensing distances shown in the coverage pattern. This must be considered when planning
the number of sensors and their placement. It is also recommended to place the sensor 4 to 6 feet
away from air supply ducts as rapid air currents or the differences in temperatures may cause false
activations.
Mount the sensor to the ceiling. The CI-305 sensors are designed for a ceiling height of about 8-10
feet. Mounting above or below this range will significantly affect the coverage patterns. Be aware
that as you decrease the mounting height, you decrease the range and increase the sensitivity to
smaller motions. Conversely, when you increase the height, you increase the range and decrease
the sensitivity to smaller motions. At heights of more than 12-14 feet, you may start to significantly
reduce sensitivity. As a general rule, each occupant should be able to clearly view the sensor.
Often the best location to install a CI- 305 in a closed office is off-center. Avoid placing a sensor directly in
line with an open door through which it has a clear view out, as the sensor may detect people walking by.
Open Office Area Coverage
To get complete coverage in an open office area, install multiple sensors so that there is an overlap
with each adjacent sensor's coverage area.
For open office areas with partitions it is best to place sensors over intersection of four workstations.
For large areas of coverage use multiple sensors.
Masking the PIR Lens
Opaque adhesive tape is supplied so that sections of the PIR lens can be masked. This restricts the
sensor's view and allows you to eliminate PIR coverage in unwanted areas such as hallways outside
of the desired coverage area. Since masking removes bands of coverage, remember to take this into
account when troubleshooting coverage problems.
Wattstopper
360° Passive Infrared Low Voltage Occupancy Sensor (version 3)
with Manual On feature
Détecteur de mouvement basse tension à infra-rouge passif 360° (v3)
avec marche en mode manuel
Sensor de ocupación con tecnología infrarroja pasiva de baja tensión 360°
con función de encendido manual (v3)
Installation Instructions • Instructions d'Installation • Instrucciones de Instalación
Voltage .......................... .........18-28VDC/VAC, half wave rectified AC
Current Consumption .................................................................10 mA
Power Supply ..............................................Wattstopper Power Packs
Operating Temperature ................................ 32° to 131°F (0° to 55°C)
Time Delay Adjustment ............................... 30 seconds to 30 minutes
PIR Coverage
Sensitivity Adjustment ...................................High or Low (DIP switch)
UL & CUL Listed for use with Wattstopper Power Packs
DESCRIPTION AND OPERATION
PLACEMENT GUIDELINES
®
SPECIFICATIONS
Walk-Through Mode .............3 minutes if no activity after 30 sec.
Test Mode ........................................5 sec. upon DIP switch reset
Model CI-305 ........................................................... up to 1200ft2
Model CI-305-1 ......................................................... up to 500ft2

Publicidad

Tabla de contenido
loading

Resumen de contenidos para LEGRAND CI-305

  • Página 1 DESCRIPTION AND OPERATION The Wattstopper CI-305 360° passive infrared (PIR) occupancy sensors turn lighting systems on and off based on occupancy. The sensors can be configured to turn lighting on, and hold it on as long as the sensor detects occupancy. After no movement is detected for a user specified time (30 seconds to 30 minutes) the lights are switched off.
  • Página 2 WIRING DIRECTIONS Each Wattstopper BZ series power pack can supply power for 14 CI-305 sensors. When using more sensors than this, multiple power packs are WARNING: TURN THE POWER OFF AT THE required. CIRCUIT BREAKER BEFORE WIRING. Refer to the wiring diagram for the following procedures: Connect the low voltage: •...
  • Página 3 The CI-305 provides a 360° coverage pattern. Two lens patterns are available. The CI-305 provides up to 1200 square feet of coverage and the CI-305-1 provides up to 500 square feet of coverage. The coverage shown represents walking motion at a mounting height of 8 feet. For building spaces with lower levels of activity or with obstacles and barriers, coverage size may decrease.
  • Página 4: Dip Switch Setting

    DIP SWITCH SETTING The CI-305 has 7 DIP switches under the cover. DIP Switch Setting Chart Time Delay: Switches 1, 2, 3 Switch# The sensor will hold the lights ON as long as occupancy is detected. The time delay countdown starts when...
  • Página 5: Ordering Information

    Power Pack: 120/277VAC, 50/60 Hz, 20A Ballast/ELV/MLV/Incandescent/LED, 16A, E-Ballast/CFL/Plug Load, (BZ-250 with Hold-On and Hold-Off capability) BZ-250-347 Power Pack: 120/347VAC, 50/60 Hz, 16A Ballast/ELV/MLV/Incandescent/LED/ E-Ballast/CFL, 15A Plug Load, with Hold-On/Hold-Off capability All sensors are white. BZ series power packs supply power for up to 14 CI-305 sensors.
  • Página 6: Instructions De Placement

    Montez le détecteur sur le plafond. Les détecteurs CI-305 sont conçus pour une hauteur de plafond allant de 2,4 à 3,05 m (de 8 à 10 pi.). Placez-les à une hauteur supérieure ou inférieure à...
  • Página 7: Instructions De Câblage

    INSTRUCTIONS DE CÂBLAGE Chaque bloc d’alimentation de la série BZ de Wattstopper peut alimenter jusqu’à 14 détecteurs CI-305. Lorsque vous utilisez plus de 8 détecteurs, WARNING: TURN THE POWER OFF AT THE plusieurs blocs d’alimentation seront nécessaires. CIRCUIT BREAKER BEFORE WIRING.
  • Página 8 Le CI-305 offre une portée à 360°. Deux modèles de mouvements de lentilles sont disponibles. Le CI-305 offre une portée jusqu’à 111 m² (1 200 pi²) et le CI-305-1 une portée jusqu’à 46 m² (500 pi²). La portée indiquée dans le schéma représente un mouvement de marche à une hauteur de 2,40 mètres (8 pieds).
  • Página 9: Protection Contre La Surcharge

    ARRÊT. Cette action fournit une période de test de 10 minutes. Pendant cette période de test, la temporisation n’est que de 5 secondes. RÉGLAGE DE L’INTERRUPTEUR DIP Le CI-305 possède 7 interrupteurs DIP sous le couvercle. N° d'interrupteur N° d'interrupteur...
  • Página 10 Bloc d’alimentation: 120/347VCA, 50/60 Hz, Ballast/ELV/MLV/Incandescent/DEL/ E-Ballast/CFL 16A, Prise de courant 15A, avec une capacité de Maintien de l’état marche/Maintien de l’arrêt Tous les détecteurs sont blancs. Les blocs d’alimentation de la série BZ peuvent alimenter jusqu’à 8 détecteurs CI-305.
  • Página 11: Especificaciones

    Como regla general, cada ocupante debería poder ver el sensor claramente. A menudo, la mejor ubicación para instalar un CI-305 en una oficina cerrada es fuera del centro. No coloque el sensor directamente alineado con una puerta abierta que dé a una vista clara al exterior, dado que el sensor puede detectar a las personas que pasan caminando.
  • Página 12: Instrucciones De Cableado

    INSTRUCCIONES DE CABLEADO Cada paquete de alimentación de la serie BZ de Wattstopper puede suministrar energía a 14 sensores CI-305. Cuando se utilicen más sensores, se necesitarán varios paquetes de alimentación. Consulte el diagrama de cableado para los siguientes procedimientos:...
  • Página 13: Diagramas De Cobertura

    DIAGRAMAS DE COBERTURA El CI-305 cuenta con lentes Fresnel multicelulares de varios niveles con un campo de visión de 360°. El sensor tiene dos opciones de perfiles de lentes. El lente de alcance extendido cubrirá hasta 1200 pis cuadrados cuando se monte desde 8 a 12 pis. El lente de alta densidad o alcance reducido cubrirá...
  • Página 14: Configuración Del Interruptor Dip

    Esto proporciona un período de prueba de 10 minutos. Durante el período de prueba, la demora de tiempo es de solo 5 segundos. CONFIGURACIÓN DEL INTERRUPTOR DIP El sensor CI-305 tiene 7 interruptores DIP debajo de la cubierta. Demora de tiempo: Interruptores 1, 2, 3 Interruptor n.°...
  • Página 15: Protección Contra Sobrecarga

    PROTECCIÓN CONTRA SOBRECARGA El sensor de presencia tiene una función de protección contra sobrecarga integrada que apaga la salida del control automáticamente cuando la corriente de la carga supere 200 mA. La luz LED del sensor parpadeará rápidamente (~ 10 Hz) a fin de emitir una señal visual de una condición de sobrecarga.
  • Página 16: Información Para Hacer Pedidos

    Fuente de alimentación: 120/347VAC, 50/60 Hz, Balasto/ELV/MLV/Incandescente/LED/ Balasto eléctrico/LFC de 16A, Carga del enchufe, con capacidad de Mantener encendido/Mantener apagado capability de 15A Todos los sensores son blancos. Las fuentes de alimentación de la serie BZ proporcionan alimentación para hasta 8 sensores CI-305. WARRANTY INFORMATION INFORMATIONS RELATIVES À...

Este manual también es adecuado para:

Ci-305-1

Tabla de contenido