Ecoflam BLU 1700.1 P AB Manual De Instrucciones página 15

Quemadores de gas de aire soplado
Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

DESCRIPTION OF THE CONTROL PANEL OF THE BURNER
YEARLY INSPECTION
Periodic inspection of the burner (combustion head, electrodes, etc.) must be carried out by authorised personnel once
or twice a year, depending of use.
Before carrying out maintenance inspection on the burner, it is advisable to check its general condition and carry out
the following operations:
- Disconnect the burner from the power supply (remove the plug).
- Close the gas cock.
- Remove the burner cover, clean the fan and air intake.
- Clean the combustion head and check the position of the electrodes.
- Re-assemble the parts.
- Check the seal on the gas pipe fittings.
- Check the flue.
- Restart the burner.
- Check the combustion parameters (CO
BEFORE EACH INTERVENTION CHECK:
- That the system is supplied with power and the burner connected.
- That the gas pressure is correct and the gas cock open.
- That the control systems are correctly connected.
If all these conditions are present, start the burner by pressing the release button. Check the burner cycle.
THE BURNER WILL NOT START:
- Check the switch, thermostats, motor, gas pressure.
THE BURNER PREVENTILATES AND LOCKS AT THE END OF THE CYCLE:
- Check the air pressure and fan.
- Check the air pressure switch.
THE BURNER PREVENTILATES AND WILL NOT IGNITE:
- Check the assembly and position of electrodes.
- Check the ignition cable.
- Check the ignition transformer.
- Check the safety devices.
THE BURNER STARTS UP AND LOCKS AFTER THE SAFETY TIME LIMIT:
- Check that the phase and neutral wires are correctly connected.
- Check the gas electrovalves.
- Check the position of the detection electrode and its connection.
- Check the detection electrode.
- Check the safety devices.
THE BURNER STARTS UP AND LOCKS AFTER RUNNING FOR A FEW MINUTES:
- Check the pressure regulator and the gas filter.
- Check the gas pressure with an ammeter.
- Check the detection value (min 3 µA LGB22, 1,5µA DMG 972).
7
I
0
MAINTENANCE
= 9.5 to 9.8),(O = less than 75 ppm).
2
pag.15
LB 472 Blu 1700.1÷2000.1 P AB B
1
1 - fuse
2
2 - termal lock-out lamp
3 - 1 st. stage working lamp
3
4 - 2 nd. stage working lamp
4
5 - high-low flame switch
5
6 - main switch I / O
7 - reset key
6

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Blu 2000.1 p ab

Tabla de contenido