Lcd Display Select Button; Operation ( Special Conditions ); Operation On Bypass-Voltage Out Of Range - Tripp-Lite SmartOnline SU20K3/3 Manual Del Propietário
Momentarily press the "SELECT" button on the front panel to browse through different power readings on the LCD Display.
BYPASS
OUTPUT
R: XXXV R: XXX.XV
(Bypass & Output Voltage)
S: XXXV
S: XXX.XV
T: XXXV
T: XXX.XV
Press "SELECT" Button
OUTPUT
LOAD
R: XXX%
XXX.XA
(Output Load & Current)
S: XXX%
XXX.XA
T: XXX%
XXX.XA
Press "SELECT" Button
MAINS
INVERTER
R: XXXV
R: XXX.XV
(Mains & Inverter Voltage)
S: XXXV
S: XXX.XV
T: XXXV
T: XXX.XV
Press "SELECT" Button
BYPASS:
XX.X Hz
MAINS:
XX.X Hz
(Bypass, Mains, Output & Inverter Frequency)
OUTPUT:
XX.X Hz
INVERTER: XX.X Hz
Press "SELECT" Button
CHARGE
FLOATING
CHARGER: XXX.XV
(Charger Mode, Charger/Battery Voltage & Battery Percentage)
BATTERY: XXX.XV
BATTERY: XXX.X%
Press "SELECT" Button
SN:
XXX
DC BUS:
XXV - XXV
(Serial Number, DC BUS Voltage, Temperature & Firmware Version)
TEMP:
XXX.X˚C
VERSION:
XXX
Press "SELECT" Button
ON:
UPS START
OFF:
UPS BYPASS
(Button Functions)
SEL:
UPS MESSAGE
ENT:
SET UPS
Press "SELECT" Button
5. Operation ( Special Conditions )
5.1 Operation On Bypass—Voltage Out Of Range
While in Bypass Mode, the UPS monitors the input voltage, which on Bypass equals the output voltage. If the output voltage passes out of an acceptable
range (between 15% higher and 20% lower than nominal), the UPS displays the condition on its LCD and stops supplying output power to its load. If
power levels return to an acceptable level, the UPS resumes supplying power to the load, and its LCD reports that output voltage was too high or too low