MASKING THE INFRARED LENS (for ATD and ATP/AHP series sensors only)
This procedure is only required for applications where the passive infrared coverage pattern must be modified to prevent the pattern from extending out of
doorways into corridors. Three masks are provided with the sensors (one way sensors include 2 masks). Select the correct mask for the application based on
the descriptions below.
Using the Conference Room Mask
0 5 10 15 20 25 30 35 40 45
0
5
10
15
20
25
30
This mask is used
35
when a Hubbell-DT is
40
45
mounted in the center
of a long rectangular
room (i.e. conference rooms). The mask provides a more
rectangular infrared pattern and prevents any spillage out
doorways at the sides of the room.
To install the selected lens, remove the lens retainer ring and lens. Insert the mask behind the lens. Be
certain to orient the mask properly to achieve the desired results. Replace the lens and lens retainer.
AMBIENT LIGHT LEVEL CONTROL OPTION (for models followed by RP suffix only)
The sensor is factory preset to turn the lights on regardless of the ambient light (natural light) level. Setting the ambient light level control will prevent the lights
from turning on when the ambient light is above the set level. The ambient light must be at the desired level to properly set this feature. To set the ambient light
level control:
1. Turn the black timer knob fully counter clockwise to the 8 second test mode.
2. Adjust the blue photocell knob fully clockwise. This will keep the lights off regardless of the ambient light.
3. Leave the sensor's coverage area. The lights should turn off after about 8 seconds.
4. When the lights turn off, re-enter the area.
5. Slowly turn the blue photocell knob counterclockwise until the lights turn on.
The sensor is now set to prevent the lights from turning on when the ambient light level is above the set threshold.
ISOLATED RELAY OPTION (for models followed by RP suffix only)
The isolated relay can be used to interface the sensor with an auxiliary system. Normally open and normally closed contacts are available. For normally open
contacts, utilize the yellow/white and blue/white wires. For normally closed contacts, utilize the black/white and blue/white wires.
SENSOR CONTROLS & MODIFICATIONS
Hubbell Adaptive Technology sensors are designed to optimize performance by automatically adjusting the sensitivity and time delay to meet the application.
The sensor controls can be modified for custom operation. The modification options are outlined below.
Bank A DIP
Switches
Infrared
Sensitivity (Red)
Timer
(Black)
Knob Color:
Function
Control
Green:
Sets the ultrasonic range
Ultrasonic
Sensitivity
Red:
Sets the infrared range
Infrared
Sensitivity
Black:
Sets the length of time
Timer
lights will remain on after
last motion is sensed
Blue:
Sets level of daylight
Daylight
needed to prevent the lights
Leveling
from turning on
**When a function is set to "Automatic Operation", the initial setting is determined by the position of the knob, CCW is counter-clockwise, CW is clockwise
PD1463
(PAGE 2)
Using the 180º Mask
The 180º mask is best
suited for an over-
the-door installation.
When the sensor is
installed inside the threshold of a doorway, you must
prevent the infrared coverage from spilling into the
adjacent corridor. New infrared pattern shown above.
Ultrasonic
Sensitivity
(Green)
Daylight Leveling
(Blue) Off
Bank B DIP
Switches
Automatic Operation
Sensor analyzes room
and sets sensitivity to
optimal setting
Same as above
Timer setting generally
increased during learning
period, then decreases to
minimize "ON" time
No automatic operation
03/15
0 5 10 15 20 25 30 35 40 45
0
5
10
15
20
25
This mask is scored on
30
the inside so it is easy
35
40
to achieve the perfect
45
mask for any application.
Simply trim away the
sections where coverage is necessary and leave the
portions where you want to prevent coverage. Lines on the
coverage pattern above represent the scores in the mask.
Purpose
B
Strong airflow
Bank
Compensator
1
Over Doorway Mounting
2
3
Automatic/Manual Timer
4
off on
Sensitivity Adjust
Purpose
A
Manual Override
Bank
1
Threshold
2
3
Motion Indicator Override
4
Reset learned settings
off on
Conditions Analyzed in
Knob Setting Under
Automatic Operation
Manual Operation**
Air currents
Linear range setting
False-on occurrences
Full CCW = min (off)
False-off occurrences
Full CW = max range
Room (surface) temp.
Same as above
Lens dirt
Signal-to-noise ratio
False-off occurrences
Linear range setting
Error free operation de-
Full CCW = min (8 sec.)
creases the timer setting
Full CW = max (40 min)
N/A
Linear range setting
Full CCW = min daylight
Full CW = max (off)
Using the Cutout Mask
0 5 10 15 20 25 30 35 40 45
0
5
10
15
20
25
30
35
40
45
Off
On
Normal or very low
Strong airflow present
airflow
Sensor mounted away
Sensor mounted over
from door
doorway
Timer set automatically
Manual timer setting
OFF = Auto
ON = Manual
Off
On
Full automatic operation
Manual lights on
Auto Threshold Adjust
High Sensitivity
LED flash when presence
Disable LED lights
is detected
Normal
Toggle On and Off
Recommended
Manual Setting
50%
75%
33%
10 min.
Off
unless
used