5.2 Changing the parameter setting

1. press the right-hand/grey key to change the
parameter setting by one value at a time
2. to input numerical values, select first the decade with the
left-hand/red key
3. the decade blinks
5.3 Parametereinstellung übernehmen und auf den
nächsten Parameter weiterschalten
1. Linke/rote Taste gedrückt halten
5.4 Programmng the adjustable parameters
5.4.1 Input signal type
Range
Selection in the menu
5.4.2 Reference point compensation
A thermoelectric temperature measurement measures a
(thermoelectric) voltage generated by a thermoelectric cou-
ple. The value of the thermoelectric voltage depends on the
temperture difference between the measured point and the
reference point.
In order to define accurately the temperature at the measu-
red point, the temperature of the reference point must be
constant and/or known. To do so, the internal and external
reference points are differentiated.
For the internal reference point compensation, the device is
fitted with an internal temperature sensor that measures
the current temperature of the terminal. This temperature is
Zumutbare Änderungen aufgrund technischer Verbesserungen vorbehalten.
Pepperl+Fuchs GmbH 68301 Mannheim Telefon (0621)776-11 11 Telefax (0621)776-27-11 11 Internet http://www.pepperl-fuchs.com
Thermoelectric couple J
Thermoelectric couple K
Thermoelectric couple N
4. set now the numerical value using the right-hand/grey
key
5. to reach the following decade, press the left-
hand/red key
6. if negative numerical values are required, set the left de-
cade to "–" or "–1".
2. and press simultaneously the right/grey key..
Note :
The fields with a grey background
contain the factory-set default va-
lues.
used to compensate the measured thermoelectric voltage.
This measuring method requires to connect the sensor with
the terminal of the display by means of appropriate com-
pensation lines. These terminals are the internal compen-
sation point.
When using the external reference point compensation, the
temperature of the reference point is maintained at a con-
stant and known value by means of appropriate measures.
The temperature sensor ist connected with the device,
which is set to the constant temperature of the reference
point, by means of a simple copper wire.