USER SET MENU
Access to the list of parameters on entering the user menu
N
Code
U00
StA
U01
StF
U02
bnF
U03
StC
U04
bnC
CSt
U05
U06
SF1
U07
tF1
U08
SF2
U09
tF2
U10
SC1
8
Name
Min
Default Max
Season
0
0
Cooling
-20.0
7.0
setpoint (°C)
Cooling band
1.0
5.0
(°C)
Heating
25.0
45.0
setpoint (°C)
Heating band
1.0
5.0
(°C)
Setpoint
0
0
correction
Cooling
-20.0
12.0
setpoint 1 (°C)
Outside air
temperature at
-40.0
18.0
cold1 (°C)
Cooling
-20.0
7.0
setpoint 2 (°C)
Outside cooling
air temperature
-40.0
30.0
2 (°C)
Heating
15.0
45.0
setpoint 1 (°C)
Meaning
If 0 - the machine works in cold mode, unless the contact operating mode is
forced.
1
If 1 - works in hot mode. If this parameter is changed while the machine is
operating, it is automatically switched off and switched on again with the
operating mode selected.
26.0
Setpoint temperature used in the cooling mode.
20.0
Temperature band used with cooling mode.
Setpoint temperature used in the heating mode.
*The maximum limit can be configured using the parameter(t) in the menu
Parameter N30
with PSW=30.
The maximum limit becomes 70° if the parameter(8) =4 to allow setpoint en-
try to adjust the boiler.
20.0
Temperature band used with heating mode
SF1
SF2
3
SF1: user set (U06);
SF2: user set (U08);
TF1: user set (U07);
TF2: user set (U09);
For hot and cold operation the operating set is calculated automatically
in relation to the outside temperature based on the logic explained in the
charts.
Visible only with the setpoint correction enabled. Set to cold 1 = tempera-
26.0
ture as per parameter 7.
Visible only with the setpoint correction enabled. Outside air temperature 1
50.0
corresponds to set at cold 1 parameter 6.
Visible only with the setpoint correction enabled. Set to cold 2 = tempera-
26.0
ture as per parameter 9.
Visible only with the setpoint correction enabled. Outside air temperature 2
50.0
corresponds to set at cold 2 parameter 8.
Visible only with the setpoint correction enabled. Set to hot 1. Set to hot
used as first extreme between which the set can be changed.
*The maximum limit can be configured using the parameter(t) in the menu
Parameter N30
with PSW=30.
The maximum limit becomes 70° if the parameter(8) =4 to allow setpoint
entry to adjust the boiler.
SC1
SC2
TF1
TF2
SC1: user set (U10);
SC2: user set (U12);
TC1: user set (U11);
TC2: user set (U13);
TC1
TC2