Megger OTS60SX Guia Del Usuario página 11

Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

Output voltage
Test Frequency
Transformer rating
Output disconnection
Power supply
Fuses
Operation
Display
Measurement Accuracy
Controls
Safety
EMC
Operational uncertainties
Temperature Range
Humidity Range
Dimensions
Weight
Cleaning
Specification
0 - 60 kV rms
61,8 Hz
500 VA
Within 1 ms of detection of breakdown
115 V (99 - 132 V), 230 V (198 - 264 V) (switch selectable) 50/60 Hz, 80 VA
500 mA (T) HBC to IEC127/5 for 220/240 V supply
1 A (T) HRC to IEC127/5 for 110/120 V supply
Mains power cord fused plug (when applicable): 3 Amp to BS1362
Semi automatic with 0,5, 2 or 3 kV/s selectable rate of voltage rise
Pause function with automatic 1 minute timer for Withstand testing
0,0 - 60,0 kV LED digital display
HV on LED
Ramp rate LED
2% ± 3 digits
Start, Pause, Stop, Ramp Rate select and Power On/Off switch
The instrument meets the requirements of IEC 61010-1
In accordance with IEC 61326-1
Refer to www.megger.com
Operating:
0 to 40 ºC
Storage:
-40 to +70 ºC
Operating:
80% RH at 40 ºC
Storage:
93% RH at 40 ºC, 95% RH at 25 ºC
336 mm (13,2 in) (H) x 400 mm (5,7 in) (L) x 235 mm (9,3 in) (D)
17,5 kg (38,5 lb)
Wipe disconnected test set with a clean cloth dampened with soapy water or Isopropyl Alcohol (IPA)