IECEx Installation drawing 5437QI01-V4R0
IECEx Certificate
Standards:
For safe installation of the 5431D..,5434D.., 5435D.. and 5437D.. the following
must be observed.
Marking
Ex ia Installation
Hazardous Area
Zone 0, 1, 2, 20, 21, 22 and M1
Terminal:
3,4,5,6,7,8,9
Uo: 7.2 VDC
Io: 12.9 mA
Po: 23.3 mW
Lo: 200 mH
Co: 13.5μF
IECEx DEK 16.0029X
IEC60079-0:2011, IEC60079-11:2011,
IEC60079-15:2010, IEC60079-7:2015
Ex ia IIC T6...T4 Ga or
Ex ib [ia Ga] IIC T6...T4 Gb
Ex ia IIIC Da
Ex ia I Ma
Unclassified Area
5437V101-ES
31