Technical Parameters; Control Description; Language Settings; Battery Replacement - Elko EP SHT-6 Manual Del Usuario

Tabla de contenido

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

  • MEXICANO, página 33

Technical parameters

Supply terminals:
Supply voltage:
Burden (max.):
Max. dissipated power
(Un + terminals):
Supply voltage tolerance:
Output
Number of contacts:
Rated current:
Switching capacity:
Peak current:
Switching voltage:
Mechanical life:
Electrical life (AC1):
Time circuit
Real time back-up:
Accuracy
- without DCF receiver:
Minimum interval:
Data stored for:
Program circuit
Number of memory places:
Program:
Data readout:
Other information
Operating temperature:
Storage temperature:
Electrical strength:
Operating position:
Mounting:
Protection degree:
Overvoltage category:
Pollution degree:
Max. cable size (mm
2
):
Dimensions:
Weight
Standards:
Warning
Device is constructed for connection in 1-phase main alternating current voltage and must
be installed according to norms valid in the state of application. Connection according to the
details in this direction. Installation, connection, setting and servicing should be installed by
qualifi ed electrician staff only, who has learnt these instruction and functions of the device.
This device contains protection against overvoltage peaks and disturbancies in supply. For
correct function of the protection of this device there must be suitable protections of higher
degree (A, B, C) installed in front of them. According to standards elimination of disturbancies
must be ensured. Before installation the main switch must be in position "OFF" and the device
should be de-energized. Don´t install the device to sources of excessive electro-magnetic
interference. By correct installation ensure ideal air circulation so in case of permanent
operation and higher ambient temperature the maximal operating temperature of the device
is not exceeded. For installation and setting use screw-driver cca 2 mm. The device is fully-
electronic - installation should be carried out according to this fact. Non-problematic function
depends also on the way of transportation, storing and handling. In case of any signs of
destruction, deformation, non-function or missing part, don´t install and claim at your seller it
is possible to dismount the device after its lifetime, recycle, or store in protective dump.
Internal circuits and sensor circuits are not galvanically isolated from the mains. No product
circuits, including sensor circuits, can be considered as ELVs.
Cable shield to the sensor, fulfi lls a functional purpose in terms of EMC does not fulfi ll any
protection or safety function and it is not associated with any EP protection. It is not possible
to touch the shield as well as the other product wiring circuits!
Security against electric shock is ensured by reinforced insulation product, cable, sensors and
their correct and professional installation.
The cable must be of a suitable dimension to meet the parameters to provide protection in the
area of the over-voltage category III.
 
SHT-6
A1 - A2
AC 230 V / 50 - 60 Hz
8 VA / 0.7 W
3.5 W
-15 %; +10 %
1x changeover (AgSnO
)
2
16 A / AC1
4000 VA / AC1, 384 W / DC
30 A / < 3 s
250 V AC / 24 V DC
7
> 3x10
> 0.7x10
5
up to 3 years
max. ± 1 s / day at 23 °C (73 °F)
1 min.
min. 10 years
100
daily, yearly (up to year 2099)
LCD display, with back light
-10.. +55 °C (14 to 131 °F)
-30.. +70 °C (-22 °F to 158 °F)
4 kV (supply - output)
any
DIN rail EN 60715
IP10 terminals,
IP40 from the front panel
III.
2
max. 2x 2.5, max. 1x 4
with sleeve max. 1x 2.5, max. 2x 1.5 (AWG 12)
90 x 35 x 64 mm (3.5˝ x 1.4˝ x 2.5˝)
114 g (4 oz.) - without battery
EN 61812-1, EN 61010-1

Control description

Device diff ers short and long button press.
In the manual marked as:
- short button press (< 1s)
- long button press (> 1s)
After 30s of inactivity (from the last press of any button) will device automatically returns into
starting menu.

Language settings

Auto
PRG
Prog
Prog
Prog
time/date
options
language
+ _
OK
options
language
selection

Battery replacement

You can change the battery without disassembling the device.
CAUTION
- only change the battery when the device is disconnected from power supply!!!
- the date and time must be reset after changing the battery!!!
- remove the plug-in module with the battery
- replace the original battery
- enter a new battery so that its upper edge (+) lines up with the plug-in module
- slide the plug-in module in the device and pay attention to polarity (+ up) - for roughly 1 s, the
display will show the name and the software version
- you can connect the device to power supply
2/4
entrance into programming menu
PRG
browsing in menu
+ _
setting of values
quick shifting during setting of
+ _
values
entrance into required menu
OK
confi rmation
one level up
ESC
a step back
back to the starting menu
ESC
Prog
ESPAnOL
Prog
Prog
Prog
OK
Prog
+ _
Prog
Prog
language
OK
ESC
- long press (>1s)
- short press (<1s)
+
CR2032

Publicidad

Tabla de contenido
loading

Tabla de contenido