Service and Maintenance
Engineers Forms
Commissioning/Field settings record sheet (continued from the previous page)
Main remote controller screen
Service menu
en
*1 The settings related to Zone2 can be switched only when 2 zone temperature control is enabled (when DIP SW2-6 and SW 2-7 are ON).
*2 For the model without both booster and immersion heater, it may not reach the set temperature depending on the outside ambient temperature.
*3 The lower limit is -15°C depending on the connected outdoor unit.
*4 The lower limit is -13°C depending on the connected outdoor unit.
*5 The lower limit is -14°C depending on the connected outdoor unit.
*6 On: the function is active; Off: the function is inactive.
*7 When DIP SW1-1 is set to OFF "WITHOUT Boiler" or SW2-6 is set to OFF "WITHOUT Mixing tank", neither Boiler nor Hybrid can be selected.
*8 Valid only when operating in Room temp. control mode.
*9 "*" of "*/kWh" represents currency unit (e.g. € or £ or the like)
*10 Valid only when operating in Heating room temperature.
*11 If asterisk (**) is chosen freeze stat function is deactivated. (i.e. primary water freeze risk)
*12 The settings related to Zone2 can be switched only when 2-zone temperature control or 2-Zone valve ON/OFF control is active.
*13 Cooling mode settings are available for ER model only.
*14 When DIP SW5-2 is set to OFF, the function is active.
*15 When the cylinder unit is connected with a PUMY-P outdoor unit, the mode is fixed to "Normal".
*16 When the cylinder unit is connected with a PUMY-P outdoor unit, the mode is fixed to "Ambient".
*17 Do not change the setting since it is set according to the specification of flow sensor attached to the cylinder unit.
31
Energy
Electric heater
Booster heater 1
monitor
capacity
capacity
settings
Booster heater 2
capacity
Immersion heater
capacity
Analog output
Delivered energy adjustment
Water pump input
Pump 1
Pump 2
Pump 3
Pump 4
Electric energy meter
Heat meter
External in-
Demand control (IN4)
put settings
Outdoor thermostat (IN5)
Thermo ON output
Parameters
0 - 30 kW
0 - 30 kW
0 - 30 kW
0 - 30 kW
−50 - +50%
0 - 200 W or ***(factory fitted pump)
0 - 200 W
0 - 200 W
0 - 200 W
0.1/1/10/100/1000 pulse/kWh
0.1/1/10/100/1000 pulse/kWh
Heat source OFF/Boiler operation
Heater operation/Boiler operation
Zone1/Zone2/Zone1&2
Default
Field
Notes
setting
setting
2 kW
4 kW
0 kW
0 kW
0%
***
0 W
0 W
72 W
1 pulse/kWh
1 pulse/kWh
Boiler
operation
Boiler
operation
Zone1&2