1=3. SELECTING OPTIONAL
DIFFERENT=DIAMETER
JOINTS
If the diameter of connection
pipe does not match the port size of outdoor unit, use optional different-diameter
joints according to the following
table.
Port size of outdoor unit
MXZ-3B
MXZ-4B
Liquid / Gas
A UNIT
6.35 (t/4) / t2.7 (t/2)
B- C UNIT B- D UNIT
6.35 (t/4) / 9.52 (3/8)
(Unit: mm (inch))
Optional different-diameter
joints (port size of outdoor unit _ diameter of connection
pipe)
6.35 (I/4) _ 9.52 (3/8) : PAC-493PI
9.52 (3/8) _
12.7 (t/2) : MAC-454JP
9.52 (3/8) _ 15.88 (5/8) : PAC-SG76RJ
12.7 (t/2) _ 9.52 (3/8) : MAC-A455JP
12.7 (t/2) _ 15.88 (5/8) : MAC-A456JP
Refer to the installation
manual of indoor unit for the diameter
of connection
pipe of indoor unit.
1-4. SELECTING THE INSTALLATION
LOCATION
Where it is not exposed
to strong wind.
Where airflow is good and dustless.
Where rain or direct sunshine can be avoided as much as possible.
Where neighbours
are not annoyed by operation sound or hot air.
Where rigid wall or support is available
to prevent the increase of operation
sound or vibration.
Where there is no risk of combustible
gas leakage.
When installing the unit, be sure to secure the unit legs.
Where it is at least 3 m (10 ft.) away from the antenna
of TV set or radio.
Operation
of the air conditioner
may interfere with radio or TV reception
in
areas where reception is weak. An amplifier may be required for the affected
device.
Install the unit horizontally.
Please
install it in an area not affected
by snowfall
or blowing
snow.
In
areas with heavy snow, please
install a canopy, a pedestal
and/or some
baffle boards.
Note:
It is advisable
to make a piping loop near outdoor
unit so as to reduce vibra-
tion transmitted
from there.
Note:
When
operating the air conditioner
in low outside
temperature,
be sure to
follow the instructions
described
below.
• Never install the outdoor unit in a place where its air inlet/outlet
side may
be exposed directly to wind.
• To prevent exposure
to wind, install the outdoor unit with its air inlet side
facing the wall.
• To prevent exposure to wind, it is recommended
to install a baffle board on
the air outlet side of the outdoor unit.
Avoid the following
places for installation
where air conditioner
trouble is li-
able to occur.
Where flammable
gas could leak.
Where there is much machine oil.
Salty places such as the seaside.
Where sulfide gas is generated such as a hot spring.
Where there is high-frequency
or wireless equipment.
Where there is emission of high levels of VOCs, including
phthalate
com-
pounds, formaldehyde,
etc., which may cause chemical cracking.
FREE SPACE REQUIRED AROUND OUTDOOR UNIT
1. Obstacles
above
When there is no obstacle in front and on the sides of the unit, it is allowed
to install the unit where an obstacle
is above the unit only if the space
shown in the figure is provided.
100 (3-15/16) or more
500 (19-11/16) .......
I _
3.
Obstacles
in front
(blowing)
only
When there is an obstacle
in front of the unit as shown in the figure, open
space above, behind, and on the sides of the unit is required.
I 500 (19-11/16)
or more
_\\\\\\\\\\\\\\_
5.
Obstacles
in front,
behind
and on side(s)
• When installing the unit in an area that is enclosed with walls such as a
verandah,
be sure to have enough space as shown below.
In this case, the air conditioning
capacity and power consumption
might
deteriorate.
• When installing two or more units, do not install the units in front or be-
hind each other.
200 (7-7/8) or more
100 (3-15/16)
350 (13-25/32)
or more
or more
.500 (19-11/16)
or more
2.
Front
(blowing)
side
open
As long as space indicated in the figure is provided,
it is allowed to install
the unit where obstacles are behind and on the sides of the unit. (No ob-
stacle above the unit)
200 (7-7/8) or more J
Z//////////////////_
100 (3-15/16) or more _h L
_
350 (13-25/32) or more
4. Obstacles
in front
and behind
The unit can be used by attaching an optional outdoor blowing guide
(MAC-856SG)
(but both sides and top are open).
_100
(3-15/16) or more
_0
(19-11/16) or more
"//////3_///////.,
Blowing guide (MAC-856SG)
6. Service
space
Provide space for service and maintenance
as shown in the figure.
Service space
Height of the obstacle
is 1200 (47-1/4) or less
(Unit: mm (inch))
En-2