2.1 PREPARATION
Before installing the device, prepare the tools required for securing it to the wall and to
make the electrical connections. The following are also required:
1. expansion wall plugs dia. 6 mm
2. Skintop type PG16 cable clamps
3. a multipole switch with a minimum contact opening of 3 mm
4. an emergency pushbutton
5. approved cables for external use with minimum cross-section of 0.75 and 1.5 mm²
2.2 ASSEMBLY
It is not necessary to drill any holes to fit the device.
1. Secure the device at a minimum height of 30 cm, using the securing holes in the
plastic container.
2. Insert the connecting cables, through the holes in the bottom of the container and the
cable clamps indicated.
3. Fit a multipole switch upstream of the device.
4. Fit an emergency pushbutton in a position where the automation system can be seen
and so that the power supply to the system can be completely cut-off.
5. Use 1.5 mm² section cables for the motor power supply and 0.75 mm² section cables
for 24 VDC devices.
6.
The device is not fitted with peak capacitors; use the ones supplied with the operators, or
order the capacitors separately as indicated in the operator's instructions.
2.3 ELECTRICAL CONNECTIONS
CAUTION
- Make sure that the mains power supply is turned OFF before making the
connections.
CAUTION
- The electrical system must comply with standards in the country where it
is installed. Use certified materials. The system must only be installed by
skilled personnel.
CAUTION
- Ensure that there is a good earthing system. Always connect it to the
relative terminals.
CAUTION
- Do not use intercom or telephone cables.
Make the electrical connections as indicated in the diagram alongside.
N.B. Bundle the low tension cables (next to the K2 terminal board), the power cables (next
to the K1 terminal board) and the earth cables (next to the K4 terminal board) securely
together.
ENGLISH
K1
1
Ph.
230 V ~
2
N
3
Common motor
4
Close motor
5
Open motor
K2
+ 24 VDC
6
- 24 VDC common
7
Start
8
Stop
9
Photocell
10
Motor limit switch
11
Open safety photocell / Closing command
12
Warning light - max 3 W
13
LED flashing
14
+ 24 VDC (shared by light and LED)
15
K4
Functional earth
N.B. The N.C. type safety contacts, that is, terminals 9 (stop), 10 (photocell), 11 (motor
limit switch) and 12 (opening safety device), must be jumpered if not used.
Protect with differential switch
6 A overload 30 mA
Light 230 VCA
Caution: preflashing is not possible
with this connection
6