Installation
PARAMETER
FEATURE
NUMBER
ALARM OR
DEFROST
108
SELECTION
FROST DELTA SP
109
RESET COMP RUN
110
TIME
FLOW SWITCH
111
STATUS
HEAT CLIMATIC
112
NUMBER
HEAT WSP
113
ECO HEAT T° RED
114
COOL WSP
115
ECO COOL T° RED
116
COOL CLIMATIC
117
NUMBER
REGION T° O
118
HEATING
STOP H T° O
119
HEATING
NO HEAT T W1
120
HEATING
MAX W T° W1
121
HEATING
MAX REGION T°
122
COOLING
COOL STOP T°
123
COOLING
MIN COOL W T°
124
COOLING
MAX COOL W T°
125
COOLING
OAT INSTALLED
126
CDU T°O
127
REFRIG T° TC
128
SUCTION T°
129
DISCHARGE T°
130
DESCRIPTION
This parameter will select the output on
J7 Pin4.
1. With this configuration J7PIN4 is HIGH if there
are activated any Unit alarms &/or Defrost
2. With this configuration J7PIN4 is HIGH if there
are activated any Unit alarms
This parameter is defining the delta set point
versus MIN COOL WT to activate the frost
threshold limit °C (KGEL)
This parameter is to give reset the compressor
time to zero
This parameter will display the Flow Switch
status:
1. Water Flowing
0. Water not flowing
Selection of Heat Climatic Curve Number:
0. No predefined Climatic Curve
(Installer has to draw Climatic Curve)
1 - 6. See Climatic curve details
Fixed Heating Water Set Point in case of the
System is not used with the Comfort NUI
Temperature reduction value for fixed HEAT
Water Set Point (ECO)
Fixed Cooling Water Set Point in case of the
system is not used with the Comfort NUI control
Temperature reduction value for fixed COOL
Water Set Point (ECO)
Selection of Cool Climatic Curve number:
0. No predefined Climatic Curve
(Installer has to draw Climatic Curve)
1 - 2. See Climatic curve details
Minimum outdoor Temperature depending on
the country where the system is installed
The system stop to heat when the outdoor
Temperature is equal or greater than the value of
this parameter
In heating mode, minimum water Temperature
going to terminal zone 1
In heating mode, maximum water Temperature
in terminal zone 1
Max region outside Temperature depending on
the Country where the system is installed
The system stop to Cool when the outdoor
Temperature is equal or superior to the value of
this parameter
In Cool mode, minimum water Temperature
In Cool mode, max water Temperature
1. GMC OAT sensor installed
2. GMC OAT sensor not installed
Outdoor Temperature value measured
by the CDU sensor
Coil refrigerant value measured by the CDU
Compressor Suction Temperature
Compressor Discharge Temperature
VALUE
DEFAULT
RANGE
VALUE
Min
Max
1
2
2
0
6
0
000
165
000
Read
0
1
status
0
6
0
20°C
60°C
45°C
1°C
20°C
5°C
4°C
25°C
7°C
1°C
10°C
5°C
0
2
0
-20°C
10°C
-7°C
10°C
30°C
20°C
20°C
60°C
40°C
20°C
60°C
55°C
24°C
46°C
40°C
0°C
30°C
22°C
4°C
20°C
4°C
4°C
20°C
12°C
1
2
2
-
-
-
-
-
-
-
-
-
-
-
-
INSTALLER
VALUE
7