SYSTEM PARAMETERS

System address. Defines the number of the system within your installation. The value 1 is shown by default. The
system will display the available values (max = 247).
Temperature range. Selects the highest temperature in heating mode (19-30 ºC) and the lowest temperature in
ES
cooling mode (18-26 ºC). It is also possible to disable some of the modes. The highest temperature by default is 30ºC.
The lowest temperature by default is 18ºC.
EN
Type of opening. Use this to activate/deactivate the proportionality in the dampers of the system. The proportionality
adjusts in 4 steps the damper opening or shutting based on the temperature demand of the zone, regulating the flow.
FR
It is configured as All/nothing by default.
*Note: If you change this parameter, all the dampers of the installation will be affected. It is not recommended for RINT and
IT
RIC intelligent grilles.
Relay settings. Use this parameter to change the operation logic of the CMV/Boiler of the system main control board.
(By default CMV)
PT
Q-Adapt (only for Think thermostats). It allows you to select the flow control algorithm that best suits your installation.
These are the available options:
DE
-
Maximum: The system operates at maximum speed, irrespective of the number of zones.
-
Power: The speed of the system is higher than in standard mode to increase the flow.
-
Standard: Mode by default. The system automatically regulates the speed based on the number of zones.
-
Silence: The speed of the system is lower than in standard mode to reduce the noise.
-
Minimum: The system operates at minimum speed, irrespective of the number of zones.
Wireless module. It activates/deactivates the wireless association module of the system.
Information (only for Think thermostats). Displays information about:
-
Zone: Firmware, zone, association, actuator o communications status.
-
System: Firmware, configuration and information about the controllers.
-
Devices: Displays what elements are connected to the system.

ZONE PARAMETERS

Associated outputs. It displays and allows you to select the control outputs associated with the thermostat.
Thermostat settings. Use this parameter to define the thermostat as Master or Zone.
*Note: It cannot be configured as Master if there is already another Master thermostat.
Use mode. The thermostats can be set in Basic or Advanced mode. They are set in advanced mode by default. These
are the parameters you can control in basic mode:
-
On/Off.
-
Set-point temperature.
-
Fan Speed
If you need to reset the thermostat to advanced mode, access the advanced configuration menu and then activate the
advanced use mode.
Control stages. This parameter is used to configure both cooling and heating stages in a single zone or in all the zones.
These are the features to be configured:
-
Air: It activates the heating/cooling air in the zone.
-
Off: It deactivates the cooling/heating stage in the zone.