SYSTEM PARAMETERS
•
System address. Defines the number of the system within your installation. The value 1 is shown by default. The
system will display the available values (max = 247).
•
Temperature range. Selects the highest temperature in heating mode (19-30 ºC) and the lowest temperature in
ES
cooling mode (18-26 ºC). It is also possible to disable some of the modes. The highest temperature by default is 30ºC.
The lowest temperature by default is 18ºC.
EN
•
Type of opening. Use this to activate/deactivate the proportionality in the dampers of the system. The proportionality
adjusts in 4 steps the damper opening or shutting based on the temperature demand of the zone, regulating the flow.
FR
It is configured as All/nothing by default.
*Note: If you change this parameter, all the dampers of the installation will be affected. It is not recommended for RINT and
IT
RIC intelligent grilles.
•
Relay settings. Use this parameter to change the operation logic of the CMV/Boiler of the system main control board.
(By default CMV)
PT
•
Q-Adapt (only for Think thermostats). It allows you to select the flow control algorithm that best suits your installation.
These are the available options:
DE
-
Maximum: The system operates at maximum speed, irrespective of the number of zones.
-
Power: The speed of the system is higher than in standard mode to increase the flow.
-
Standard: Mode by default. The system automatically regulates the speed based on the number of zones.
-
Silence: The speed of the system is lower than in standard mode to reduce the noise.
-
Minimum: The system operates at minimum speed, irrespective of the number of zones.
•
Wireless module. It activates/deactivates the wireless association module of the system.
•
Information (only for Think thermostats). Displays information about:
-
Zone: Firmware, zone, association, actuator o communications status.
-
System: Firmware, configuration and information about the controllers.
-
Devices: Displays what elements are connected to the system.
ZONE PARAMETERS
•
Associated outputs. It displays and allows you to select the control outputs associated with the thermostat.
•
Thermostat settings. Use this parameter to define the thermostat as Master or Zone.
*Note: It cannot be configured as Master if there is already another Master thermostat.
•
Use mode. The thermostats can be set in Basic or Advanced mode. They are set in advanced mode by default. These
are the parameters you can control in basic mode:
-
On/Off.
-
Set-point temperature.
-
Fan Speed
If you need to reset the thermostat to advanced mode, access the advanced configuration menu and then activate the
advanced use mode.
•
Control stages. This parameter is used to configure both cooling and heating stages in a single zone or in all the zones.
These are the features to be configured:
-
Air: It activates the heating/cooling air in the zone.
-
Off: It deactivates the cooling/heating stage in the zone.
44