Installation
Vernatherm Ajustment Instructions
NOTE: The Vernatherm TMA valve is NOT factory preset. Upon installation, the temperature
of this valve must be checked and adjusted to ensure delivery of a safe water temperature.
Water in excess of 110°F (43°C) may cause scalding.
A
CHECK THE TEMPERATURE AND ADJUST IF NECESSARY (THE RANGE OF THE VALVE IS 95°F–115°F (35°C–43°C). TO ADJUST THE
TEMPERATURE, FOLLOW THE PROCEDURE BELOW:
LOOSEN TEMPERATURE LOCKING NUT WITH WRENCH.
USING A BLADE SCREWDRIVER, TURN THE ADJUSTMENT STEM COUNTERCLOCKWISE TO INCREASE THE TEMPERATURE OR
CLOCKWISE TO DECREASE THE TEMPERATURE (FIGURE 10).
ONCE DESIRED TEMPERATURE IS REACHED, TIGHTEN NUT TO PREVENT TEMPERATURE CHANGE.
B
CLEAN SPRAYHEAD IF NECESSARY. SEE PAGE 19 FOR SPRAYHEAD MAINTENANCE AND REPAIR PARTS. ADJUST THE VOLUME
CONTROL VALVE, IF NECESSARY, TO CONTROL THE FLOW OF WATER.
C
ATTACH PEDESTAL ACCESS PANEL WITH HARDWARE PROVIDED.
Bradley Corporation • 215-1332 Rev. U; EN 10-00-002
TEMPERATURE
ADJUSTMENT
STEM
Figure 10
TEMPERATURE
LOCKING
NUT
1-26-10
TDB3103, WF3203
13

Publicidad

loading

Este manual también es adecuado para:

Tdb3103